www.poolpak.com | 800-959-7725
18
| ComPak
®
Series - Installation, Operation and Maintenance
Technical Summary
Table 2-1. RoofComPak® Technical Data
Dimensional Data
Figure 2-2. PCP RoofComPak® Dimensions
RoofComPak
®
Weights
AWH/HCDH 3500/4000 with integral gas or electric heat, remote ACC
2900 lbs
AWH/HCDH 3500/4000 with integral gas or electric heat, integral ACC
3700 lbs
AWH/HCDH 3500/4000 with no integral auxiliary heat, integral ACC
2700 lbs
MODEL NUMBER
AWH / HCDH 3500 - 10 TON
AWH / HCDH 4000 - 12 TON
Pool Size (Sq. Ft.)
1,200 - 2,000
1,400 - 2,500
Reheat Capacity (MBH)
170
200
Moisture Removal (Lb/Hr@82°F/60%RH)
63
70
Pool Water Flow (GPM)
26
28
Pool Water Condenser PD (FT WC)*
20
30
Pool Water Condenser Capacity (MBH)
170
200
Outside Air (CFM)(Nominal)
0 - 2,800
0 - 2,800
Total Supply Airflow CFM (Maximum)
3,500 - 8,000
4,000 - 8,000
Refrigerant Charge (lbs)
81
83
Dimensions (in inches) with integral air-cooled condenser and gas furnace
Length
264
264
Width
57.4
57.5
Height
52.5
52.2
OA
45.3
15.2
13.4
44.0
FRONT VIEW
52.5
SA
120.0 C.G.
* Side return air available; horizontal return air available without integral air-cooled condenser
LEFT VIEW
RA*
264.0