ComPak
®
Series IOM
DOC# SVW06-STARTUP-20170630
5
POOL WATER HEATING – AW UNITS ONLY (HCD UNITS SKIP TO AIR COOLING MODE)
___ 1. Verify that there is a wire connecting to the ground lug labeled “POOL BONDING LUG” and that the
rest of the wet metal surfaces from the pool system (boiler, lights, ladder, etc.) have been bonded to
each other and then to ground.
NOTE: Improperly bonded metal components or piping are prone to galvanic corrosion and will
not be covered under warranty.
___ 2. If present, start the ComPak secondary loop pool water pump.
___ 3. To place the controller into Demand Control Mode: Press the PRG (
) button. The screen will show
“Main Menu – Status Screens”. Press the UP ARROW (
) to select “Main Menu – Service” and then
press the ENTER (
↵
) button. “Password Required” is displayed. Use the UP ARROW (
) to change
the number to:
0005
and press the ENTER (
↵
) button.
Press the UP ARROW (
) to select “Main Menu – Service – Manual Mode” and then press the
ENTER (
↵
) button. “Password Required” is displayed. Use DOWN ARROW (
) to change the number
to:
9995
and press the ENTER (
↵
) button. The display should show “Main Menu – Service – Manual
Mode – Demand Control”. Press the ENTER (
↵
) button.
Press the ENTER (
↵
) button to move the cursor next to “
POOL HEAT
”. Press the UP ARROW (
) to
change it from NO to
YES
and press ENTER (
↵
).
___ 4. After 5 minutes, press the PRG (
) button. The screen will show “Main Menu – Status Screens”.
Press ENTER (
↵
) then press the DOWN ARROW (
) and record the following data:
SPACE TEMP:
°
F
OUTSIDE TEMP (Economizer units only):
°
F
SPACE RH:
%
SPACE DEWPOINT:
°
F
POOL TEMP (AW models only)
°
F
___ 5. Press the PRG (
) button. The screen will show “Main Menu – Status Screens”. Press the DOWN
ARROW (
) until “Main Menu – Detailed Status” is displayed and then press ENTER (
↵
). Press the
DOWN ARROW (
) and record the following data:
SURFACE TEMP:
°
F
DISCH PRESS:
PSIG
DEWPOINT:
°
F
SUCT PRESS:
°
F
DEWPOINT SETPOINT:
°
F
SUCT TEMP:
°
F
SUCT SH:
°
F
AIR COOLING MODE
If equipped with an
integrated (factory installed)
air-cooled condenser, skip to Step 2 below.
If equipped with a
remote
air-cooled or water-cooled condenser, verify that the air-cooled or water-cooled
condenser and refrigerant piping has been pressure tested to at least 450 PSI and then placed into a vacuum.
use a recovery machine to add the necessary field refrigerant charge to the A/C lineset or condenser. The
additional oil should be added to the suction line while the compressor is operating in A/C mode. Refer to the
IOM or contact PoolPak Service for assistance in calculating the required field refrigerant and oil amounts.