www.poolpak.com | 800-959-7725
60
| ComPak
®
Series - Installation, Operation and Maintenance
• BASRtnTempSetp: This value indicates the space temperature set point being requested by the BAS interface.
It is provided for troubleshooting only and should not need to be modified.
• BASRtnRHSetp: This value indicates the space humidity set point being requested by the BAS interface.
It is provided for troubleshooting only and should not need to be modified.
• BASPoolTempSetp: This value indicates the pool temperature set point being requested by the BAS interface.
It is provided for troubleshooting only and should not need to be modified.
• BASForcePurge: Off or On. This value indicates the whether the BAS is requesting purge mode operation.
It is provided for troubleshooting only and should not need to be modified.
• BASForceNoPurge: Off or On. This value indicates the whether the BAS is requesting non-purge mode
operation. It is provided for troubleshooting only and should not need to be modified.
MULTI-UNIT NETWORK
This menu contains parameters that configure the operation of dehumidifier in a multiple unit installation. Default
values are shown in bold-faced type:
• Network Control: No or Yes. This parameter indicates whether the dehumidifier should participate in multi-unit
coordination.
• Staged Dehum: No or Yes. This parameter indicates whether the unit should participate in the first or second
stage of dehumidification. When set to No, the unit will start dehumidification immediately when required.
A setting of Yes will cause the dehumidifier to participate in the second stage as determined by the next
parameter.
• Stg2 DH Offset: 4.0˚F (Range 0.0 – 9.9˚F). This parameter indicates how far the dew point must rise above
set point before the unit energizes the compressor for the second stage of dehumidification.
• Pool Temp Ctl: Local or Network. This parameter indicates whether the unit should control pool temperature
based on the network requirement or its own internal temperature sensor. A setting of Local should be used
if this dehumidifier is connected to a different pool than the rest of the units on the network.
COMPRESSOR
This menu contains parameters that configure the operation of the dehumidifier compressor. Default values are
shown in bold-faced type:
• Air Temp Limits: No or Yes. This parameter indicates whether the space temperature must be between
60 and 105 ˚F to allow compressor operation. Do not change this parameter to No unless instructed by
factory service.
• Anti-cycle Time: 5 minutes (Range 1 – 9 minutes) This parameter indicates how long the compressor must
remain off before it can be restarted. It defaults to 5 minutes after every power cycle. Do not change to less
than 5 minutes unless instructed by factory service.
• LP Cutout: 40 PSI (Range 0 – 99 PSI). This parameter indicates the suction pressure at which the compressor
will be shut down with a low pressure fault. Do not change this parameter unless instructed by factory service.
• LP Cutout Dif: 15 PSI (Range 0 – 99 PSI). This parameter indicates how far the suction pressure must rise
above the cutout setting before the compressor will be re-enabled after a low pressure fault.
• LPCO Byp Tim: 120s. Do not change this parameter without PoolPak service authorization.
• Cmpr Enabled: Yes or No. This parameter should typically be set to Yes. Do not set to No unless instructed
by factory service.
ECONOMIZER
This menu contains parameters that configure the operation of the optional field provided and field installed
economizer damper system. Default values are shown in bold-faced type:
• OA/RA Min Dif: 5.0˚F (Range 2.0 – 9.9˚F) This parameter indicates how much the outside air temperature
must be below the return air temperature to allow economizer operation.
• Min OA Temp: 50.0˚F (Range 40.0 – 60.0˚F). This parameter indicates the lowest outside air temperature
allowed for economizer operation.