www.poolpak.com | 800-959-7725
88
| ComPak
®
Series - Installation, Operation and Maintenance
DOC# SVW06-STARTUP-20170630
6
NOTE: Failure to add the correct amount and type of refrigerant and oil will void the warranty.
If equipped with
remote
or
integrated
water-cooled condenser for air cooling, verify water flow is present. On a
chilled water condenser, verify that the bypass valve over the water-regulating valve is
OPEN
.
___ 1.
Open the ball valves to the A/C condenser (not present on RoofComPak integrated ACC).
___ 2. To place the controller into Demand Control AIR COOL Mode: Press the PRG (
) button. Press the
UP ARROW (
) to select “Main Menu – Service” and then press the ENTER (
↵
) button. “Password
Required” is displayed. Use the UP ARROW (
) to change the number to:
0005
and press the ENTER
(
↵
) button.
Press the UP ARROW (
) to select “Main Menu – Service – Manual Mode” and then press the
ENTER (
↵
) button. “Password Required” is displayed. Use DOWN ARROW (
) to change the number
to:
9995
and press the ENTER (
↵
) button. The display should show “Main Menu – Service – Manual
Mode – Demand Control”. Press the ENTER (
↵
) button.
Press the ENTER (
↵
) button to move the cursor next to “
CMPR HEAT
”. Press the UP ARROW (
) to
change it from YES to
NO
and press ENTER (
↵
).
Press the ENTER (
↵
) button to move the cursor next to “
AIR COOLING
”. Press the UP ARROW (
)
to change it from NO to
YES
and press ENTER (
↵
).
___ 3. After 10 minutes, press the PRG (
) button. The screen will show “Main Menu – Status Screens”.
Press ENTER (
↵
) then press the DOWN ARROW (
) and record the following data:
SPACE TEMP:
°
F
OUTSIDE TEMP (Economizer units only):
°
F
SPACE RH:
%
SPACE DEWPOINT:
°
F
POOL TEMP (AW models only)
°
F
___ 4. Press the PRG (
) button. The screen will show “Main Menu – Status Screens”. Press the DOWN
ARROW (
) until “Main Menu – Detailed Status” is displayed and then press ENTER (
↵
). Press the
DOWN ARROW (
) and record the following data:
SURFACE TEMP:
°
F
DISCH PRESS:
PSIG
DEWPOINT:
°
F
SUCT PRESS:
°
F
DEWPOINT SETPOINT:
°
F
SUCT TEMP:
°
F
SUCT SH:
°
F
Amount of refrigerant added:
Lbs. Compressor oil:
Type:
Amount:
Oz.
Lineset info: Total length:
Ft.
Pipe Size:
” Vapor
” Liquid
Condenser Elevation:
Ft. Circle one:
Above or
Below
ComPak unit.
NOTE: Failure to add the correct amount and type of refrigerant and oil will void the warranty.