The device should be installed on a stable non-flammable surface. Gas insert is equipped with a special feet
(B - Picture 2) with the possibility of adjusting their height (from 60 to 150 mm) and two adjustable mounting
brackets (A - Picture 2) to allow attachment of the device to the wall. The mounting brackets (A) are used to
maintain the minimum distance from non-combustible walls. It is forbidden to install gas insert without a
minimum distance from the rear or side wall. The Assembly is allowed only vertically.
Picture 2 - Location of wall mounting brackets and adjustable feet
5.6.
Fireplace housing execution
Before performing the installation, protect the elements of the gas control system from dirt. Installation of
the fireplace, according to current building regulations should be made of non-combustible materials
(including floor and ceiling). If the fireplace is powered by natural gas (NG), exhaust grille should be placed
under the ceiling of the room where the device is installed. Power liquid propane - butane (LPG) requires from
the installer placing the exhaust grilles next to the floor, above ground level in the room in which the device
is installed.
To perform the installation of the fireplace housing, you should use non-combustible and heat-resistant
materials, including its upper part, material in its interior and behind the device.
WARNING!
The device must not be used as a supporting construction - it cannot keep the weight of the
fireplace wall.