58
SM6
2006
Interval of timed Interrupt no. 1
SM7
2007
Interval of timed Interrupt no. 2
These words define the interval for timed interrupts.
Value of interval may be set between 1 and 100 ms
(example: SM6=1
1 ms SM6=100
100 ms). For
SM6 and SM7 values not included between 1 and
100, the default setting of relevant interrupt is 100 ms.
At starting the values are fixed as 100
100 ms.
R/W
SM8
2008
Status digital inputs I1÷I16 for test cycle
This word gives the status of digital inputs during test
(SM0.5=1). Each bit of these words refers to the
status of one digital input, starting with less significant
bit (SM8.0
I1, SM8.15
I16). This word is
automatically set to zero at the starting of EPL101.
R/W
SM9
2009
Min. value analog output AQ1
The value of analog output ) for which the Volt output
must be 0,0V. This word is directly modified using the
instruction RANGE(AQx,Min,Max). Automatically set
to zero at starting.
R/W
SM10
2010
Max value analog output AQ1
The value of analog output AQ1 ) for which the volt
output must be 5,0V. This word is directly modified
using
the
instruction
RANGE(AQ1,Min,Max).
Automatically set to 500 at starting
R/W
SM11
2011
Value of analog output AQ1
Values of this word definse the value of output AQ1.
The tension value of output is given by the formule
below AQ1(volt) = ((SM10-SM11)/(SM10-SM9))*5,0
Setting the output value equals to minimum limit,
output will be 0,0 volt; setting the value equals to max.
limit, the output will be 5,0 volt.
If output value is not included in the interval
Minimum<Value<Maximum, the value for rating volt
output is automatically reset within the minimum and
maximum limit.
Automatically set to zero at starting
R/W
SM20
2020
Countings of counter bidirectional encoder 1 (high area)
SM21
2021
Countings of counter bidirectional encoder 1 (low area)