62
SM50
2050
Max value for Analog input AI3 linear
SM51
2051
Max value for Analog input AI4 linear
Set the minimum and maximum numeric limits for
analog conversion of inputs AI configured as current
or tension. These words are modified using the
instruction RANGE (AIx,Min,Max). Default settings at
starting is 0 for minimum value and 1000 for maximum
value.
R/W
SM52
2052
Offset calibration Analog input AI1
SM53
2053
Offset calibration Analog input AI2
SM54
2054
Offset calibration Analog input AI3
SM55
2055
Offset calibration Analog input AI4
SM56
2056
Gain calibration Analog input AI1
SM57
2057
Gain calibration Analog input AI2
SM58
2058
Gain calibration Analog input AI3
SM59
2059
Gain calibration Analog input AI4
These words define the calibration of conversion for
AI1, AI2, AI3 , AI4. They are used to correct eventual
mistakes of reading. The formule is as follows:
Value AIx = Value AIx + (Value AIx * Gain calibration
AIx) / 1000 Offset calibration AIx.
At starting all calibration values are set to zero.
R/
W
SM60
2060
Value Analog input AI1
SM61
2061
Value Analog input AI2
SM62
2062
Value Analog input AI3
SM63
2063
Value Analog input AI4
Numeric values of analog inputs AI obtained rating
between minimum, maximum values, the conversion
and the values of offset and gain.
R
SM64
2064
Volt value for input I1
SM65
2065
Volt value for input I2
SM66
2066
Volt value for input I3
Value of tension which is measured on digital inputs
I1..I3. Range is 0..10V and it is available with two
decimal points.
R
SM82
2082
Offset of protocol address EPL101
This value is added to the value obtained from the
combination of jumpers used to select the address.
Default setting at starting is 1.
R/W
SM83
2083
Status of dip switches for address selection
Value obtained by the combination of dip switches for
R