Wiring
Operating Manual PSENvip R, PSENvip R LR,PSENvip E
1003449-EN-06
| 77
6
Wiring
6.1
Notes on wiring
WARNING!
Unintended machine start up!
A unintended start may lead to serious injury and death.
Voltage should be removed from the whole machine and PSENvip during
wiring.
Please observe the following when wiring:
}
The transmitter and receiver should only be connected using shielded cables (available
as accessories). The cable shield is connected to the metal coupling on the M12 connect-
ors.
}
Earth the cable shield connection within the control cabinet, e.g. on a bus bar.
}
We recommend you use Pilz ready-made cable to connect the PSENvip (see Order refer-
ences).
}
To use the PSENvip in accordance with the requirements of UL, only use cables listed
under Category Code CYJV.
}
Protect the cable from mechanical damage. If the cable is not protected through the ma-
chine, it should be laid in armoured hose. Lay the cable in such a way that wire short cir-
cuits are excluded.
}
Avoid interference (e.g. from motors, power lines) by laying cables in a way that is EMC-
compliant.
When the wiring is complete the protective equipment will need to undergo a function test
(see Check function of protective equipment)