44
16.
Manual mode
The manual mode enables the service technician to manually activate and operate individual
components of the heating system. This special system operating mode is activated automatically as
soon as parameters of the sub masks are edited. Otherwise a direct activation is effected via the
ON/OFF switch of
Manual mode
. An activate manual mode will be displayed on the status bar via the
status icon
The duration of the manual operation is defined via the parameter "Start-up time"
(default 2 hours) and will be deactivated automatically.
16.1.
Testing of the sensors and actuators with manual mode
1.
Detail menu
►
System
►
Manual mode
:
“Manual mode” activated via ON/OFF switch.
If activated, all relays are turned off and the
icon will appear on the status bar
2.
Heating circuits
►
Heating circuits 1-4:
Return to the previous screen and enter “
Heat circuits
”
"Mixer nominal value" push the slider CLOSED/OFF/OPEN to see if the mixer settings changes.
3.
If successful, return to the main screen. If the test cause any issues, please resolve now.
4.
Press the
icon on the main screen and deactivate the manual mode.
5.
Detail menu
►
Service
►
Save/Load parameters
►
Save parameters
►
Start saving:
Backup the system configuration.
6.
Press two times
Return
and choose
Restart
:
Restart the system to accept the set configurations.
7.
The heat generating system is now ready.