11.7.
Select system operating mode
This mask is utilized to select the system operating mode. The following operating modes can
be selected via a selection dial:
The system operating mode
standby
is set as a default. In
this case, the set operating modes of heating circuits, hot-
water tank, solar system and photovoltaic are deactivated
and the heat generator is not active but the frost
protection will remain active.
An active system operating mode must first be selected for the entered settings on the heating circuits
to take effect. Available options are the
automatic mode
or the
hot water mode
.
For the
hot water mode
system mode, the heating circuits are turned off (frost protection remains
active), hot-water tanks, solar systems and photovoltaic are turned on.
In the
automatic
system mode, heating circuits and cooling circuits, hot-water tanks, solar systems,
and photovoltaic frost protection are activated.
From this system mode also the two options
automatic heating
and
automatic cooling
are available,
which only have one type of temperature distribution circuits (heating or cooling) and one type of
buffer (heating or cooling). These system mode is also activated automatically, in case of performed
settings on the option masks of the system. This modified settings will be accepted when switching to
an active system operating mode again.
11.8.
Chimney Sweeper
This mask is used to start the chimney sweeper mode by pressing the button "start". The
mask will also show the remaining time as well as the corresponding status icon
on
the activity bar of the
Home
screen. The chimney sweeper mode is used to measure the
pollution emissions.
Type of heat source
Description
External heat source
Upon activation, the actual heat generator is stopped and
the external heat source is operated with maximum
output, up to 2 hours (see displayed Remaining time).
The chimney sweeper function can be terminated by the
operator at any time, otherwise the function ends
automatically after the indicated remaining time expires.
At that time, the system returns to its original operating
mode.
Information
The mask
external heat source
is only visible in case of activated option "Has emissions" in
Settings
►
Device
►
Service
►
Ext. heat source
►
Parameter
.