background image

21

ENGLISH

used. The first system is used to detect 

the base load; the air hose is connected 

to the base load switch or to the static 

pressure sensor module. The second 

measurement system is used to detect 

high water levels (when the pressure 

sensor module is used as a redundant 

system) and must be connected to the 

high water switch. The redundant sys-

tem switches the pump(s) on in the 

event of an error. The maximum per-

missible air hose length is 20 m.
It is important that the hose is laid at a 

slight downward gradient from the con-

trol unit to the chamber.

Air pressure bell sensors

The switch-on level is determined by 

the installation heights of the air pres-

sure sensors in the collecting chamber. 

Connect the blue hose to the upper 

pressure sensor for peak load/alarm!
To prevent pockets of condensed mois-

ture settling in the hose, the entire 

length of the hoses should be laid at 

an uphill gradient, rising continuously 

from the chamber to the control unit. 

Water in the hose will cause the switch-

ing points to be displaced. Also, if the 

hose is exposed to frost, the water could 

freeze and cause the switching system 

to break down!
The hoses may have a maximum length 

of 20 m. Existing hoses must not be ex-

tended due to the danger of leaks, but 

must be replaced with hoses in one 

piece.
Connect the static pressure system for 

"base load" to B1, and the "Alarm/peak 

load" (blue hose) to B2 on the control.

Dry running  

In systems in which there is an explo-

sion hazard, the pump must not be al-

lowed to run in dry conditions. Separate 

dry running protection must therefore 

be installed. A submersible switch 

is connected to terminals 18/20 via a 

safety barrier. The submersible switch 

remains closed if there is a high wa-

ter level. If the water level sinks to the 

height of the pump volute casing, the 

submersible switch opens and both 

pumps are switched off.

Rechargeable battery

The control unit can be fitted with a 9V 

NI-MH rechargeable battery. This ena-

bles a high water alarm to be triggered 

even if there is a power failure.

CAUTION!

Only use the 9V-NiMh battery supplied by 
the manufacturer! If dry-cell batteries or 
Lithium batteries are used there is a dan-
ger of explosion!

NOTICE!

 Check the function of the bat-

tery pack at regular intervals! The ser-
vice life is about 5 to 10 years. Note the 
insertion date on the battery pack and 

after five years the battery pack should 

be replaced as a precautionary measure.

Software update

The control unit has a programming 

interface that allows new software ver-

sions to be installed. If a new software 

version becomes available, the control 

unit software can be updated on-site 

by JUNG PUMPEN service personnel, 

without dismantling the unit.

EMC

When used in connection with our 

standard submersible pumps and ac-

cessories, and when installed correct-

ly and used for its intended purpose, 

the control unit meets all protective 

requirements of the EMC Directive 

2014/30 EU and is suitable for domestic 

and commercial use when connected 

to the public power supply network. If 

connected to an industrial power sup-

ply network within an industrial facility, 

where the power supply is provided by 

an in-house high-voltage transformer, 

there  may  be  insufficient  immunity  to 

interference.

Summary of Contents for JUNG PUMPEN HIGHLOGO 1-00

Page 1: ...anvisning JUNG PUMPEN HIGHLOGO HIGHLOGO 1 25 LC HIGHLOGO 1 46 LC HIGHLOGO 1 610 LC HIGHLOGO 2 25 LC HIGHLOGO 2 46 LC HIGHLOGO 2 610 LC HIGHLOGO 1 00E HIGHLOGO 1 00 HIGHLOGO 1 25 HIGHLOGO 1 46 HIGHLOGO...

Page 2: ...2...

Page 3: ...f hrlicher F rderg ter z B ex plosiv giftig hei m ssen so abgef hrt werden dass keine Gef hrdung f r Personen und die Umwelt entsteht Gesetzliche Be stimmungen sind einzuhalten Sicherheitshinweise f r...

Page 4: ...teuerung mit einem konti nuierlichen Niveaumesssystem Stau drucksensor oder Tauchsonde be trieben so werden die gemessenen Niveaus direkt verarbeitet und ausge wertet Arbeitet die Steuerung mit Schwim...

Page 5: ...Display erscheint der Fehlertext ab wechselnd mit der Standardanzeige Sollten mehrere Fehler aufgetreten sein werden diese Meldungen nachei nander angezeigt Zus tzlich wird der Hochwasseralarm an ein...

Page 6: ...G Das Passwort lautet im Auslieferungszustand 3197 Wird das Passwort ge ndert und dann verges sen muss das Ger t vom Werkskun dendienst des Herstellers freigeschal tet werden Ein R cksetzen durch den...

Page 7: ...wird Der Wert f r die maximale Laufzeit ist bei den techni schen Daten der Pumpe zu finden Die anschlie ende Pausenzeit Einschalt sperre in der die Pumpe abgeschaltet wird muss so lang sein dass der...

Page 8: ...ereich von 1 bis 60 Minuten bei Eingabe von 0 Minuten ist diese Funk tion deaktiviert Bei digitaler Niveauerfassung und geschlossenem Kontakt an Klem me 27 28 erfolgt eine zeitverz ger te akustische A...

Page 9: ...DIENST Hier kann die Rufnummer des zust ndi gen Kundendienstes hinterlegt werden Update Nur f r den Kundendienst des Herstel lers St rmeldungen Erkennt die Steuerung eine St rung so wird ein Alarm erz...

Page 10: ...der Steuerung die Schrauben l sen und die Geh uset r ffnen Das Display ist empfindlich gegen mechanischen Ein fluss Gestrichelte Verbindungen auf dem Schaltplan m ssen bauseits erstellt werden Netz Al...

Page 11: ...rstand bleibt der Tauchschalter geschlossen Sinkt der Wasserstand auf die H he des Pumpenringgeh uses ffnet der Tauchschalter und beide Pumpen wer den abgeschaltet Der Trockenlaufschutz ist eine wicht...

Page 12: ...mindestens 1x pro Jahr bzw 2x j hrlich in gewerblich ge nutzten Anlagen auf korrekte Funktion gepr ft werden 1 Pumpe einschalten mit dem Hand 0 Automatik Wahltaster auf Hand Bei Doppelanlagen ist die...

Page 13: ...9 0 9 0 12 0 A 2 5 4 0 4 0 6 3 6 3 10 0 6 3 10 0 A berwachung Drehfeld Phasenausfall bei Linksdrehfeld und bei Ausfall einer Phase erfolgt Meldung Temperaturbereich Betrieb 20 50 C Temperaturbereich...

Page 14: ...cal en ergy must be prevented Leakages of dangerous e g explosive toxic hot substances must be discharged such that no danger to people or the environment occurs Legal regulations must be observed Saf...

Page 15: ...urement system static pressure sensor or submersible sensor the levels that are measured are processed and evaluated directly If the control unit operates using float switches the switching status of...

Page 16: ...that When using the control unit the re spective national laws regulations local regulations and the rules of the local energy utility are adhered to The system is professionally secured The level det...

Page 17: ...rom the lower edge of the pressure bell High water level only for SM and HD This menu item is used to define which level of water in the collecting chamber should trigger an alarm The value is defined...

Page 18: ...ctly 10 cm above the volute casing of the pump A test run must be carried out to check that the follow up time function operates correctly Start up delay This is for maintaining staggered oper ation i...

Page 19: ...elay time has elapsed the integrated buzz er if activated sounds and the red error LED lights up Two alarm outputs are available a non isolated alarm relay alarm output 1 protected by an inter nal fus...

Page 20: ...block The pump cable wires marked 30 32 motor thermal contacts must be attached to terminals 30 32 for pump 1 and pump 2 separately Motor protection switch The control unit is fitted with a motor pro...

Page 21: ...onditions Separate dry running protection must therefore be installed A submersible switch is connected to terminals 18 20 via a safety barrier The submersible switch remains closed if there is a high...

Page 22: ...ghLogo 1 25 46 610 910 HighLogo 2 25 46 610 910 2 5 4 0 4 0 6 0 6 3 9 0 9 0 12 0 A 2 5 4 0 4 0 6 3 6 3 10 0 6 3 10 0 A Monitoring of rotational field phase failure Error message given for anti clockwi...

Page 23: ...system blocked Check refer to pump manual Motor contactor does not switch through all phases Replace Motor fault Call customer service personnel Backpressure water rising slowly Intake line blocked Cl...

Page 24: ...v m tsystem mottryckssensor eller dyksond bearbetas de uppm tta niv erna direkt och utv rderas Om styrningen arbetar med flott rer best mmer flott rernas kopplingstill st nd om pumpen kopplar OBS Niv...

Page 25: ...vara riktigt anslutna Om anl ggningen anv nds i ett explosionsfarligt schakt m ste alla g llande f reskrifter f r drift av anl ggningar i explosionsfarliga omr den beaktas Str mkretsarna f r sensorik...

Page 26: ...tartas l ptids vervakningen f r pumpen V rde i cm vattenpelare m tt fr n underkant mottrycksklocka resp dyksond Mottrycksmodul Digitalt system med tv tryckbrytare och tv tryckluftklockor f r 1 Grundla...

Page 27: ...ll vid kontinuerlig niv m tning Hos en del installationer vill man inte att mediet r kvar i beh l laren f r l nge eller att det verl mnas till det sammanlagda systemet vid en viss tidpunkt Dessutom ka...

Page 28: ...t Ett separat h gvattenlarm kan anslutas som V xelkontakten utan potential kan belastas med max 5A 250V AC Felmeddelanden Vridf lt Inget h gervridf lt ligger an H gvattenlarm Om den uppm tta ni v n li...

Page 29: ...kten 50 51 52 f r separat versv mningslarm r max lastbar med 5A 250V AC Rel et arbetar enligt principen om ppen krets dvs om det finns ett fel tar rel et upp Niv registrering Om styrningen drivs med e...

Page 30: ...ktriker F re varje ingrepp m ste appa raten g ras sp nningsl s t ex genom att f rs kringarna los sas Anl ggningen g r inte varken i au tomatisk eller manuell drift N tsp nning saknas kontrollera s kri...

Page 31: ...e HighLogo 1 25 46 610 910 HighLogo 2 25 46 610 910 2 5 4 0 4 0 6 0 6 3 9 0 9 0 12 0 A 2 5 4 0 4 0 6 3 6 3 10 0 6 3 10 0 A vervakning vridf lt fasbortfall vid v nstervridf lt eller bortfall av en fas...

Page 32: ...32 HighLogo 1 00 E...

Page 33: ...30 32 an X3 P1 zu Br cken 9V Akku BT1 Hochwasser alarm I P1 HighLogo AUX 1 Motor schutz Pumpe 1 Getrennt GL AUS Potentialbehaftetes Alarmrelais Netzanschluss Pumpe 1 F1 6 3AT F2 2AT K4 L1 30 K1 BRX L...

Page 34: ...eichnete Verbindungen sind bauseits zu erstellen Der Luftschlauch f r die Niveauerfassung ist mit stetigem Gef lle zum Schacht zu verlegen 1 9V Akku BT1 Alarmrelais Sammelst r meldung Hochwasser alarm...

Page 35: ...35 HighLogo 1 LCXS...

Page 36: ...36...

Page 37: ...rstands Messung 0 5kOhm Reset Taster AUX 1 Motor schutz Pumpe 1 Motor schutz Pumpe 2 Getrennt GL AUS KT T GL SL HW I P2 50Hz Netz 1 N PE x 230V 1 5mm 1 K3 K2 Alarmrelais Sammelst r meldung max 5A 230V...

Page 38: ...38 HighLogo 2 00 2 910 1...

Page 39: ...39 HighLogo 2 00 2 910 2...

Page 40: ...40 HighLogo 2 LC 1...

Page 41: ...41 HighLogo 2 LC 2...

Page 42: ...42 HighLogo 2 LCXS 1...

Page 43: ...43 HighLogo 2 LCXS 2...

Page 44: ...er opz Q1 Opt main Switch Inter principal Fac Hoofdschakelaar Int principale F1 Safety barrier Barri re s curit Veiligheidsbarr Barr sicurezza SUOMI SVENSKA POLSKI Netz Verkkoliit nt N tanslutning Pod...

Page 45: ...eneral Manager R diger Rokohl Sales Manager 2011 65 EU RoHS 2014 30 EU EMC EN 55014 1 2006 A2 2011 EN 55014 2 1997 A2 2008 EN 61000 3 2 2014 EN 61000 3 3 2013 2014 35 EU LVD EN 60204 1 2006 AC 2010 EN...

Page 46: ...der eigen verantwoordelijkheid dat het product voldoet aan de gestelde richtlijnen PL Z pe n odpowiedzialno ci o wiadczamy e produkt odpowiada postanowieniom wymienionych dyrektyw RO Declar m pe propr...

Page 47: ...47...

Page 48: ...JUNG PUMPEN GmbH Industriestr 4 6 33803 Steinhagen Deutschland Tel 49 5204 170 Fax 49 5204 80368 eMail kd jung pumpen de...

Page 49: ...Stromkreis Die Barriere wird im Geh use der Pum pensteuerung untergebracht und verdrahtet Einsetzbar in die Pumpensteuerungen AD 23 910 X AD 25 910 XM AD 8 XME AD 12 XME BD 23 910 X BD 25 910 XM HIGHL...

Page 50: ...h her montieren WARTUNG Der Trockenlaufschutz ist eine wichtige Sicherheitseinrichtung f r den Explosionsschutz und muss mindestens 1x pro Jahr und in gewerblich genutzten Anlagen 2x pro Jahr auf korr...

Page 51: ...he following pump control units AD 23 610 X AD 25 610 XM AD 8 XME AD 12 XME BD 23 610 X BD 25 610 XM HIGHLOGO OLD 12 2017 AD 23 610 Ex 4 AD 25 ExM 3 AD 46 610 ExM 7 AD 8 ExME 3 AD 12 ExME 4 BD 23 610...

Page 52: ...p MAINTENANCE Dry running protection is an important safety device for explo sion protection and its good working order must be checked at least once a year and in commercially used systems twice a ye...

Page 53: ...intrinseca Essa viene installata nell alloggiamento del comando pompa e cablata Pu essere utilizzata per i seguenti comandi di pompe AD 23 610 X AD 25 610 XM AD 8 XME AD 12 XME BD 23 610 X BD 25 610 X...

Page 54: ...l inter ruttore a galleggiante pi alto MANUTENZIONE La protezione contro la marcia a secco un importante dispo sitivo di sicurezza per la protezione contro le esplosioni e il suo corretto funzionament...

Page 55: ...Sicherheitsbar riere von aktiven Teilen anderer Stromkreise muss mindes tens 50 mm Fadenma betragen ELEKTRISCHER ANSCHLUSS An die eigensicheren Klemmen d rfen Stromkreise der Zone 1 oder 2 angeschloss...

Page 56: ...ll monitored environment The distance between the intrinsically safe terminals of the safety barrier and the active parts of any other electrical cir cuits must be at least 50 mm string length ELECTRI...

Page 57: ...ti a sicurezza intrinseca della barriera di sicurezza dalle parti attive di altri circuiti deve essere di alme no 50 mm misura del filo COLLEGAMENTO ELETTRICO Ai morsetti a sicurezza intrinseca possib...

Page 58: ...4...

Page 59: ...5...

Page 60: ...6...

Page 61: ...7...

Page 62: ...8...

Page 63: ...9...

Page 64: ...zodpovednos vyhlasujeme e v robok sp a po iadavky uveden ch smern c SV Vi f rs krar att produkten p v rt ansvar r utf rd enligt g llande riktlinjer CE 121 17 1811 Steinhagen 15 11 2018 ______________...

Reviews: