background image

20 

ENGLISH

Thermostat. 

The pump’s thermal con-

tact has been triggered. The pump is 

then switched off. This error must be 

acknowledged on the control unit. If 

the error condition no longer exists, 

the control unit starts up again. This 

error condition will also be saved in the 

event of a power failure. The message is 

saved in the EEPROM of the processor, 

which is zero voltage safe.

Running time. 

The maximum running 

time of the pump has been exceeded.

Sensor error. 

An error has occurred in 

the level measurement system. (Short 

circuit or interruption in the power 

supply lines to the level sensor; meas-

ured value lies outside the range 4 - 20 

mA) The pumps is switched off. If the 

high-water  float  switch  is  activated  in 

this situation, however, the pump will 

be switched on, provided that the pump 

is not faulty.

Sensor logic. 

An error has occurred in 

the level measurement system. (Incon-

sistent switching status of float switch

-

es). The pump is then switched off. If the 

high-water  float  switch  is  activated  in 

this situation, however, the pump will be 

switched on, provided that the pump is 

not faulty. This error condition will also 

be saved in the event of a power failure. 

The message is saved in the EEPROM 

of the processor, which is zero voltage 

safe.

Dry running.

 The water level is too low 

to start the pump up safely according to 

ATEX. 

ASSEMBLY

Only electricians may carry out 

electrical work! Before com-

mencing work, always ensure 

that the unit is at zero voltage by un-

screwing the pre-fuses!
When using the control, the respec-

tive national laws and regulations as 

well as local regulations on protection 

against explosion must be observed, 

such as European standards EN 60079-

0:2012:A11:2013, EN 60079-1:2014 and 

EN 1127-1:2011.
Do not install the control unit itself in 

explosion hazard areas or in the collect-

ing chamber!
The control unit must be installed only 

in well-ventilated areas - high humidity 

can destroy the control unit!
Install the unit above the local backup 

level and in a position that allows easy 

access for inspections at all times.

Please read and follow the safety in-

structions  in  the  first  section.  Loosen 

the screws and open the housing door 

to connect the control unit. The display 

is sensitive to mechanical damage. 
Dashed connections on the diagram 

must be made by the user. 

Mains:

 To provide a separate pre-fuse, 

use safety fuses: 

  

- HIGHLOGO 2-610 - 25 A, 

  

- HIGHLOGO 2-910 - 25 A,

  

- HIGHLOGO 1-910 - 20 A,

  

- HighLogo 2-00E - 20 A,

  

- HIGHLOGO 2-46 - 20 A, 

  

- All others - 16 A.

The mains power cable (5 G1.5 mm² to 

max. 5 G4 mm²) must be connected to 

terminals L1, L2, L3, N, and the PE ter-

minal block.

Connecting the pumps

The pump cable wires marked U1, V1 

and W1 must be connected up, and PE 

must be attached to the PE terminal 

block. The pump cable wires marked 

30/32 (motor thermal contacts) must be 

attached to terminals 30/32 for pump 1 

and pump 2 separately. 

Motor protection switch

The  control  unit  is  fitted  with  a  motor 

protection relay. The rated current at 

the motor protection relay must be set 

to correspond to the motor data. The 

control unit records the triggering event 

and saves it in a zero voltage safe mem-

ory. In ATEX operation, this means that – 

irrespective of an automatic reset – the 

pump cannot be operated again until 

the error has been acknowledged on 

the control unit.
The control must be opened to enable 

a motor protection RESET to be carried 

out.
If the rotating direction is correct, the 

start-up jolt of the pump is in the op-

posite direction to that shown by the 

rotational direction arrow located on 

the motor housing. If the direction of 

rotation is not correct, the two phases 

of the pump cable must be reversed on 

the control unit. 

Before starting up for the first 

time, check that the protective 

measures function properly!

Alarm contacts

 

Connect the non-isolated alarm relay to 

terminals N/X2 (normally open contact) 

or N/X3 (normally closed contact). 
Connect remote fault indication 

The potential-free change-over con-

tact (40-41-42) can be loaded with max. 

5A/250V AC. The relay operates accord-

ing to the quiescent current principle, 

i.e. the relay drops out in the event of a 

fault or voltage drop. 
The change-over contact (50-51-52) 

for separate high water alarm can be 

loaded with max. 5A/250V AC. The re-

lay operates according to the operating 

current principle, i.e. the relay picks up 

in the event of a fault.

Level detection

If the control unit is operated with a level 

sensor, the sensor must be connected 

to terminals 9(+) and 10(-). 

ATTENTION! 

Check that the poles are connected the 

right way round!
If the control unit is not operated with a 

level sensor but with switches, the switch 

for the base load must be connected to 

terminals 21(-) and 23(+). Because this 

is a simple normally open contact, the 

poles are unimportant here.
When operating with two pressure 

switches, the second pressure switch is 

to be connected to terminals 27/28. It is 

used to detect high water and the peak 

load function.
When operating with three submersible 

ball contact switches, the high water 

function and peak load functions are 

separate:

  

- Base load ON-OFF   Terminal 21/23

  

- Peak load ON-OFF   Terminal 24/25

  

- High water alarm     Terminal 27/28

If a separate OFF float switch is connec

-

ted

  

- Pump(s) OFF 

Terminal 21/22

  

- Base load ON 

Terminal 22/23

  

- Peak load ON 

Terminal 24/25

  

- High water alarm  Terminal 27/28

In explosion protected areas, however, 

submersible ball contact switches must 

be connected via an explosion protected 

auxiliary switching module.

Level measurement with the static 

air pressure system 

If the static air pressure system is 

used for measuring the water levels 

(using switches or pressure sensors), 

two measurement systems are usually 

Summary of Contents for JUNG PUMPEN HIGHLOGO 1-00

Page 1: ...anvisning JUNG PUMPEN HIGHLOGO HIGHLOGO 1 25 LC HIGHLOGO 1 46 LC HIGHLOGO 1 610 LC HIGHLOGO 2 25 LC HIGHLOGO 2 46 LC HIGHLOGO 2 610 LC HIGHLOGO 1 00E HIGHLOGO 1 00 HIGHLOGO 1 25 HIGHLOGO 1 46 HIGHLOGO...

Page 2: ...2...

Page 3: ...f hrlicher F rderg ter z B ex plosiv giftig hei m ssen so abgef hrt werden dass keine Gef hrdung f r Personen und die Umwelt entsteht Gesetzliche Be stimmungen sind einzuhalten Sicherheitshinweise f r...

Page 4: ...teuerung mit einem konti nuierlichen Niveaumesssystem Stau drucksensor oder Tauchsonde be trieben so werden die gemessenen Niveaus direkt verarbeitet und ausge wertet Arbeitet die Steuerung mit Schwim...

Page 5: ...Display erscheint der Fehlertext ab wechselnd mit der Standardanzeige Sollten mehrere Fehler aufgetreten sein werden diese Meldungen nachei nander angezeigt Zus tzlich wird der Hochwasseralarm an ein...

Page 6: ...G Das Passwort lautet im Auslieferungszustand 3197 Wird das Passwort ge ndert und dann verges sen muss das Ger t vom Werkskun dendienst des Herstellers freigeschal tet werden Ein R cksetzen durch den...

Page 7: ...wird Der Wert f r die maximale Laufzeit ist bei den techni schen Daten der Pumpe zu finden Die anschlie ende Pausenzeit Einschalt sperre in der die Pumpe abgeschaltet wird muss so lang sein dass der...

Page 8: ...ereich von 1 bis 60 Minuten bei Eingabe von 0 Minuten ist diese Funk tion deaktiviert Bei digitaler Niveauerfassung und geschlossenem Kontakt an Klem me 27 28 erfolgt eine zeitverz ger te akustische A...

Page 9: ...DIENST Hier kann die Rufnummer des zust ndi gen Kundendienstes hinterlegt werden Update Nur f r den Kundendienst des Herstel lers St rmeldungen Erkennt die Steuerung eine St rung so wird ein Alarm erz...

Page 10: ...der Steuerung die Schrauben l sen und die Geh uset r ffnen Das Display ist empfindlich gegen mechanischen Ein fluss Gestrichelte Verbindungen auf dem Schaltplan m ssen bauseits erstellt werden Netz Al...

Page 11: ...rstand bleibt der Tauchschalter geschlossen Sinkt der Wasserstand auf die H he des Pumpenringgeh uses ffnet der Tauchschalter und beide Pumpen wer den abgeschaltet Der Trockenlaufschutz ist eine wicht...

Page 12: ...mindestens 1x pro Jahr bzw 2x j hrlich in gewerblich ge nutzten Anlagen auf korrekte Funktion gepr ft werden 1 Pumpe einschalten mit dem Hand 0 Automatik Wahltaster auf Hand Bei Doppelanlagen ist die...

Page 13: ...9 0 9 0 12 0 A 2 5 4 0 4 0 6 3 6 3 10 0 6 3 10 0 A berwachung Drehfeld Phasenausfall bei Linksdrehfeld und bei Ausfall einer Phase erfolgt Meldung Temperaturbereich Betrieb 20 50 C Temperaturbereich...

Page 14: ...cal en ergy must be prevented Leakages of dangerous e g explosive toxic hot substances must be discharged such that no danger to people or the environment occurs Legal regulations must be observed Saf...

Page 15: ...urement system static pressure sensor or submersible sensor the levels that are measured are processed and evaluated directly If the control unit operates using float switches the switching status of...

Page 16: ...that When using the control unit the re spective national laws regulations local regulations and the rules of the local energy utility are adhered to The system is professionally secured The level det...

Page 17: ...rom the lower edge of the pressure bell High water level only for SM and HD This menu item is used to define which level of water in the collecting chamber should trigger an alarm The value is defined...

Page 18: ...ctly 10 cm above the volute casing of the pump A test run must be carried out to check that the follow up time function operates correctly Start up delay This is for maintaining staggered oper ation i...

Page 19: ...elay time has elapsed the integrated buzz er if activated sounds and the red error LED lights up Two alarm outputs are available a non isolated alarm relay alarm output 1 protected by an inter nal fus...

Page 20: ...block The pump cable wires marked 30 32 motor thermal contacts must be attached to terminals 30 32 for pump 1 and pump 2 separately Motor protection switch The control unit is fitted with a motor pro...

Page 21: ...onditions Separate dry running protection must therefore be installed A submersible switch is connected to terminals 18 20 via a safety barrier The submersible switch remains closed if there is a high...

Page 22: ...ghLogo 1 25 46 610 910 HighLogo 2 25 46 610 910 2 5 4 0 4 0 6 0 6 3 9 0 9 0 12 0 A 2 5 4 0 4 0 6 3 6 3 10 0 6 3 10 0 A Monitoring of rotational field phase failure Error message given for anti clockwi...

Page 23: ...system blocked Check refer to pump manual Motor contactor does not switch through all phases Replace Motor fault Call customer service personnel Backpressure water rising slowly Intake line blocked Cl...

Page 24: ...v m tsystem mottryckssensor eller dyksond bearbetas de uppm tta niv erna direkt och utv rderas Om styrningen arbetar med flott rer best mmer flott rernas kopplingstill st nd om pumpen kopplar OBS Niv...

Page 25: ...vara riktigt anslutna Om anl ggningen anv nds i ett explosionsfarligt schakt m ste alla g llande f reskrifter f r drift av anl ggningar i explosionsfarliga omr den beaktas Str mkretsarna f r sensorik...

Page 26: ...tartas l ptids vervakningen f r pumpen V rde i cm vattenpelare m tt fr n underkant mottrycksklocka resp dyksond Mottrycksmodul Digitalt system med tv tryckbrytare och tv tryckluftklockor f r 1 Grundla...

Page 27: ...ll vid kontinuerlig niv m tning Hos en del installationer vill man inte att mediet r kvar i beh l laren f r l nge eller att det verl mnas till det sammanlagda systemet vid en viss tidpunkt Dessutom ka...

Page 28: ...t Ett separat h gvattenlarm kan anslutas som V xelkontakten utan potential kan belastas med max 5A 250V AC Felmeddelanden Vridf lt Inget h gervridf lt ligger an H gvattenlarm Om den uppm tta ni v n li...

Page 29: ...kten 50 51 52 f r separat versv mningslarm r max lastbar med 5A 250V AC Rel et arbetar enligt principen om ppen krets dvs om det finns ett fel tar rel et upp Niv registrering Om styrningen drivs med e...

Page 30: ...ktriker F re varje ingrepp m ste appa raten g ras sp nningsl s t ex genom att f rs kringarna los sas Anl ggningen g r inte varken i au tomatisk eller manuell drift N tsp nning saknas kontrollera s kri...

Page 31: ...e HighLogo 1 25 46 610 910 HighLogo 2 25 46 610 910 2 5 4 0 4 0 6 0 6 3 9 0 9 0 12 0 A 2 5 4 0 4 0 6 3 6 3 10 0 6 3 10 0 A vervakning vridf lt fasbortfall vid v nstervridf lt eller bortfall av en fas...

Page 32: ...32 HighLogo 1 00 E...

Page 33: ...30 32 an X3 P1 zu Br cken 9V Akku BT1 Hochwasser alarm I P1 HighLogo AUX 1 Motor schutz Pumpe 1 Getrennt GL AUS Potentialbehaftetes Alarmrelais Netzanschluss Pumpe 1 F1 6 3AT F2 2AT K4 L1 30 K1 BRX L...

Page 34: ...eichnete Verbindungen sind bauseits zu erstellen Der Luftschlauch f r die Niveauerfassung ist mit stetigem Gef lle zum Schacht zu verlegen 1 9V Akku BT1 Alarmrelais Sammelst r meldung Hochwasser alarm...

Page 35: ...35 HighLogo 1 LCXS...

Page 36: ...36...

Page 37: ...rstands Messung 0 5kOhm Reset Taster AUX 1 Motor schutz Pumpe 1 Motor schutz Pumpe 2 Getrennt GL AUS KT T GL SL HW I P2 50Hz Netz 1 N PE x 230V 1 5mm 1 K3 K2 Alarmrelais Sammelst r meldung max 5A 230V...

Page 38: ...38 HighLogo 2 00 2 910 1...

Page 39: ...39 HighLogo 2 00 2 910 2...

Page 40: ...40 HighLogo 2 LC 1...

Page 41: ...41 HighLogo 2 LC 2...

Page 42: ...42 HighLogo 2 LCXS 1...

Page 43: ...43 HighLogo 2 LCXS 2...

Page 44: ...er opz Q1 Opt main Switch Inter principal Fac Hoofdschakelaar Int principale F1 Safety barrier Barri re s curit Veiligheidsbarr Barr sicurezza SUOMI SVENSKA POLSKI Netz Verkkoliit nt N tanslutning Pod...

Page 45: ...eneral Manager R diger Rokohl Sales Manager 2011 65 EU RoHS 2014 30 EU EMC EN 55014 1 2006 A2 2011 EN 55014 2 1997 A2 2008 EN 61000 3 2 2014 EN 61000 3 3 2013 2014 35 EU LVD EN 60204 1 2006 AC 2010 EN...

Page 46: ...der eigen verantwoordelijkheid dat het product voldoet aan de gestelde richtlijnen PL Z pe n odpowiedzialno ci o wiadczamy e produkt odpowiada postanowieniom wymienionych dyrektyw RO Declar m pe propr...

Page 47: ...47...

Page 48: ...JUNG PUMPEN GmbH Industriestr 4 6 33803 Steinhagen Deutschland Tel 49 5204 170 Fax 49 5204 80368 eMail kd jung pumpen de...

Page 49: ...Stromkreis Die Barriere wird im Geh use der Pum pensteuerung untergebracht und verdrahtet Einsetzbar in die Pumpensteuerungen AD 23 910 X AD 25 910 XM AD 8 XME AD 12 XME BD 23 910 X BD 25 910 XM HIGHL...

Page 50: ...h her montieren WARTUNG Der Trockenlaufschutz ist eine wichtige Sicherheitseinrichtung f r den Explosionsschutz und muss mindestens 1x pro Jahr und in gewerblich genutzten Anlagen 2x pro Jahr auf korr...

Page 51: ...he following pump control units AD 23 610 X AD 25 610 XM AD 8 XME AD 12 XME BD 23 610 X BD 25 610 XM HIGHLOGO OLD 12 2017 AD 23 610 Ex 4 AD 25 ExM 3 AD 46 610 ExM 7 AD 8 ExME 3 AD 12 ExME 4 BD 23 610...

Page 52: ...p MAINTENANCE Dry running protection is an important safety device for explo sion protection and its good working order must be checked at least once a year and in commercially used systems twice a ye...

Page 53: ...intrinseca Essa viene installata nell alloggiamento del comando pompa e cablata Pu essere utilizzata per i seguenti comandi di pompe AD 23 610 X AD 25 610 XM AD 8 XME AD 12 XME BD 23 610 X BD 25 610 X...

Page 54: ...l inter ruttore a galleggiante pi alto MANUTENZIONE La protezione contro la marcia a secco un importante dispo sitivo di sicurezza per la protezione contro le esplosioni e il suo corretto funzionament...

Page 55: ...Sicherheitsbar riere von aktiven Teilen anderer Stromkreise muss mindes tens 50 mm Fadenma betragen ELEKTRISCHER ANSCHLUSS An die eigensicheren Klemmen d rfen Stromkreise der Zone 1 oder 2 angeschloss...

Page 56: ...ll monitored environment The distance between the intrinsically safe terminals of the safety barrier and the active parts of any other electrical cir cuits must be at least 50 mm string length ELECTRI...

Page 57: ...ti a sicurezza intrinseca della barriera di sicurezza dalle parti attive di altri circuiti deve essere di alme no 50 mm misura del filo COLLEGAMENTO ELETTRICO Ai morsetti a sicurezza intrinseca possib...

Page 58: ...4...

Page 59: ...5...

Page 60: ...6...

Page 61: ...7...

Page 62: ...8...

Page 63: ...9...

Page 64: ...zodpovednos vyhlasujeme e v robok sp a po iadavky uveden ch smern c SV Vi f rs krar att produkten p v rt ansvar r utf rd enligt g llande riktlinjer CE 121 17 1811 Steinhagen 15 11 2018 ______________...

Reviews: