background image

18 

ENGLISH

If "manual error acknowledgement" is 

set to 'Yes' then press the OK button to 

restart the pump.

   

Short-term operation (S2 time)

When the pump is not submerged, it 

operates only for a preset period (max-

imum running time). This is to prevent 

the temperature of the motor from ris-

ing above its maximal permissible op-

erating temperature. The value for the 

maximum permissible running time can 

be found in the technical data provided 

with the pump. The subsequent resting 

time (restart lock-out), during which the 

pump remains switched off, must be 

long enough to allow the motor to cool 

down to the ambient temperature. This 

is generally equal to the operating time 

multiplied by a factor of five.

   

Intermittent duty (S3 time)

The pump operates only for a short pe-

riod before being switched off again if it 

is not submerged. The switch-on and 

switch-off times are expressed as per-

centages of 10 minutes, e.g. for an S3 

time of 30%, the pump is switched on 

for not longer than 3 minutes and then 

switched off for 7 minutes. This operat-

ing mode ensures that the pump does 

not overheat.

Follow-up time

The follow-up time is the time for which 

the pump continues to run after the 

switch-off level has been reached, to 

ensure that the pressure sensor hangs 

free of the remaining wastewater in the 

chamber. This is important because it 

prevents the measuring system from 

becoming soiled. If the “Static pressure 

sensor” setting has been selected, the 

available options are: “Standard”, “Au-

tomatic parameterisation” and “Auto-

matic”. If the “Pressure switch” and “KT 

switch” setting has been chosen, only 

the “Standard” setting is available.

   

“Standard” setting: When the wa-

ter level drops below the switch-off 

level, the pump does not switch off 

immediately, but continues to run for 

the time specified here. Adjustment 

range: from 0 to 120 seconds!

   

“Automatic” setting (static pressure 

sensor only): The time required for 

each pumping operation is recorded 

and compared with a stored value, 

and adjusted if necessary. 

   

"Automatic parameterisation” set-

ting: (static pressure sensor only) 

The follow-up time is determined 

here  from  the  first  three  pumping 

procedures.

ATTENTION!

 The switch-off point for 

explosion-protected submersible mo-

tor pumps must not be at a lower depth 

than the upper edge of the volute cas-

ing in order to comply with EU Directive 

2014/34 EC. The pump must not draw 

in air!
The correct follow-up time can be de-

termined only by carrying out several 

trial runs with the system!

The final running time of the pump can

-

not be correctly determined until the 

pressure line is full of wastewater.
When using the “Automatic follow-up 

time” function, make sure that the 

air-pressure sensor of the static pres-

sure sensor is installed at a height of 

exactly 10 cm above the volute casing 

of the pump. A test run must be carried 

out to check that the follow-up time 

function operates correctly. 

Start-up delay 

This is for maintaining staggered oper-

ation in areas with only a limited power 

supply.

­­­­­ FORCED SWITCHING ON ­­­­­

Test run

To prevent the pump from seizing up, it 

can be started up briefly at regular in

-

tervals. The start of the pumps takes 

place 1 to 7 days after the last pump run 

for 1 to 5 seconds. If the water level is 

measured using level sensors, the test 

run will only be carried out if the water 

level lies above the switch-off level.
In order to avoid unnecessary loading of 

energy use, the pumps are started with 

at least an 8-second interval from one 

another in the test run.
For control units with digital level 

measurement (submersible /pressure 

switches), it must be noted that a cer-

tain amount of water will always be 

pumped, even if the pump is switched 

on for just a second. This means that 

if no water flows into the chamber, but 

continued test runs are carried out, the 

pump could end up operating in “snore” 

mode.
This would mean non-compliance with 

explosion protection regulations and 

could also result in the need for a ser-

vice operative to be called out to bleed 

the air from the pump.

Automatic pumping out

(only for SM and) This function only 

makes sense with continuous lev-

el measurement. Some installations 

may require media to not remain in the 

chamber for too long, or it to be pumped 

into the overall system at a specif-

ic  time.  In  addition,  with  low  inflow,  it 

can ensure that open level sensors are 

freed from obstructions at regular in-

tervals (setting 1-99 hours).

­­­­­ ALARM

 -----

Acoustic alarm

If this function is enabled, the integrat-

ed alarm buzzer will be sounded when 

an error occurs. Options: Yes / No.
If an error is acknowledged with the OK 

button, the alarm will stop buzzing but 

the relay contact will remain active. By 

pressing the OK button a second time, 

the relay will be reset, provided that the 

error no longer exists.

Alarm relay flashes

You are able to select here whether the 

non-isolated alarm relay switches at 

one-second intervals when a fault oc-

curs or whether it remains on all the 

time: Yes = Relay switches at one-sec-

ond intervals, No = Relay with continu-

ous contact.

Delay for alarm relay

To prevent the alarm from being trig-

gered for errors of short duration, a 

time delay can be set here for switch-

ing the non-isolated and potential-free 

alarm contacts. Setting range from 1 to 

60 seconds. A value of 0 minutes deac-

tivates this function!

AUX logic

"AUX  in  switch  logic"  is  configured  as 

normally closed or normally open.

AUX influence

"Aux  influence"  can  be  used  to  select 

whether an alarm switches off one or 

both pumps ("P1 OFF," or "P2 OFF") or 

does not have any effect ("None"). In ei-

ther case, the triggered alarm appears 

in the display and activates the poten-

tial-free and non-isolated alarm relays 

as soon as the alarm delay time has 

expired.

Summary of Contents for JUNG PUMPEN HIGHLOGO 1-00

Page 1: ...anvisning JUNG PUMPEN HIGHLOGO HIGHLOGO 1 25 LC HIGHLOGO 1 46 LC HIGHLOGO 1 610 LC HIGHLOGO 2 25 LC HIGHLOGO 2 46 LC HIGHLOGO 2 610 LC HIGHLOGO 1 00E HIGHLOGO 1 00 HIGHLOGO 1 25 HIGHLOGO 1 46 HIGHLOGO...

Page 2: ...2...

Page 3: ...f hrlicher F rderg ter z B ex plosiv giftig hei m ssen so abgef hrt werden dass keine Gef hrdung f r Personen und die Umwelt entsteht Gesetzliche Be stimmungen sind einzuhalten Sicherheitshinweise f r...

Page 4: ...teuerung mit einem konti nuierlichen Niveaumesssystem Stau drucksensor oder Tauchsonde be trieben so werden die gemessenen Niveaus direkt verarbeitet und ausge wertet Arbeitet die Steuerung mit Schwim...

Page 5: ...Display erscheint der Fehlertext ab wechselnd mit der Standardanzeige Sollten mehrere Fehler aufgetreten sein werden diese Meldungen nachei nander angezeigt Zus tzlich wird der Hochwasseralarm an ein...

Page 6: ...G Das Passwort lautet im Auslieferungszustand 3197 Wird das Passwort ge ndert und dann verges sen muss das Ger t vom Werkskun dendienst des Herstellers freigeschal tet werden Ein R cksetzen durch den...

Page 7: ...wird Der Wert f r die maximale Laufzeit ist bei den techni schen Daten der Pumpe zu finden Die anschlie ende Pausenzeit Einschalt sperre in der die Pumpe abgeschaltet wird muss so lang sein dass der...

Page 8: ...ereich von 1 bis 60 Minuten bei Eingabe von 0 Minuten ist diese Funk tion deaktiviert Bei digitaler Niveauerfassung und geschlossenem Kontakt an Klem me 27 28 erfolgt eine zeitverz ger te akustische A...

Page 9: ...DIENST Hier kann die Rufnummer des zust ndi gen Kundendienstes hinterlegt werden Update Nur f r den Kundendienst des Herstel lers St rmeldungen Erkennt die Steuerung eine St rung so wird ein Alarm erz...

Page 10: ...der Steuerung die Schrauben l sen und die Geh uset r ffnen Das Display ist empfindlich gegen mechanischen Ein fluss Gestrichelte Verbindungen auf dem Schaltplan m ssen bauseits erstellt werden Netz Al...

Page 11: ...rstand bleibt der Tauchschalter geschlossen Sinkt der Wasserstand auf die H he des Pumpenringgeh uses ffnet der Tauchschalter und beide Pumpen wer den abgeschaltet Der Trockenlaufschutz ist eine wicht...

Page 12: ...mindestens 1x pro Jahr bzw 2x j hrlich in gewerblich ge nutzten Anlagen auf korrekte Funktion gepr ft werden 1 Pumpe einschalten mit dem Hand 0 Automatik Wahltaster auf Hand Bei Doppelanlagen ist die...

Page 13: ...9 0 9 0 12 0 A 2 5 4 0 4 0 6 3 6 3 10 0 6 3 10 0 A berwachung Drehfeld Phasenausfall bei Linksdrehfeld und bei Ausfall einer Phase erfolgt Meldung Temperaturbereich Betrieb 20 50 C Temperaturbereich...

Page 14: ...cal en ergy must be prevented Leakages of dangerous e g explosive toxic hot substances must be discharged such that no danger to people or the environment occurs Legal regulations must be observed Saf...

Page 15: ...urement system static pressure sensor or submersible sensor the levels that are measured are processed and evaluated directly If the control unit operates using float switches the switching status of...

Page 16: ...that When using the control unit the re spective national laws regulations local regulations and the rules of the local energy utility are adhered to The system is professionally secured The level det...

Page 17: ...rom the lower edge of the pressure bell High water level only for SM and HD This menu item is used to define which level of water in the collecting chamber should trigger an alarm The value is defined...

Page 18: ...ctly 10 cm above the volute casing of the pump A test run must be carried out to check that the follow up time function operates correctly Start up delay This is for maintaining staggered oper ation i...

Page 19: ...elay time has elapsed the integrated buzz er if activated sounds and the red error LED lights up Two alarm outputs are available a non isolated alarm relay alarm output 1 protected by an inter nal fus...

Page 20: ...block The pump cable wires marked 30 32 motor thermal contacts must be attached to terminals 30 32 for pump 1 and pump 2 separately Motor protection switch The control unit is fitted with a motor pro...

Page 21: ...onditions Separate dry running protection must therefore be installed A submersible switch is connected to terminals 18 20 via a safety barrier The submersible switch remains closed if there is a high...

Page 22: ...ghLogo 1 25 46 610 910 HighLogo 2 25 46 610 910 2 5 4 0 4 0 6 0 6 3 9 0 9 0 12 0 A 2 5 4 0 4 0 6 3 6 3 10 0 6 3 10 0 A Monitoring of rotational field phase failure Error message given for anti clockwi...

Page 23: ...system blocked Check refer to pump manual Motor contactor does not switch through all phases Replace Motor fault Call customer service personnel Backpressure water rising slowly Intake line blocked Cl...

Page 24: ...v m tsystem mottryckssensor eller dyksond bearbetas de uppm tta niv erna direkt och utv rderas Om styrningen arbetar med flott rer best mmer flott rernas kopplingstill st nd om pumpen kopplar OBS Niv...

Page 25: ...vara riktigt anslutna Om anl ggningen anv nds i ett explosionsfarligt schakt m ste alla g llande f reskrifter f r drift av anl ggningar i explosionsfarliga omr den beaktas Str mkretsarna f r sensorik...

Page 26: ...tartas l ptids vervakningen f r pumpen V rde i cm vattenpelare m tt fr n underkant mottrycksklocka resp dyksond Mottrycksmodul Digitalt system med tv tryckbrytare och tv tryckluftklockor f r 1 Grundla...

Page 27: ...ll vid kontinuerlig niv m tning Hos en del installationer vill man inte att mediet r kvar i beh l laren f r l nge eller att det verl mnas till det sammanlagda systemet vid en viss tidpunkt Dessutom ka...

Page 28: ...t Ett separat h gvattenlarm kan anslutas som V xelkontakten utan potential kan belastas med max 5A 250V AC Felmeddelanden Vridf lt Inget h gervridf lt ligger an H gvattenlarm Om den uppm tta ni v n li...

Page 29: ...kten 50 51 52 f r separat versv mningslarm r max lastbar med 5A 250V AC Rel et arbetar enligt principen om ppen krets dvs om det finns ett fel tar rel et upp Niv registrering Om styrningen drivs med e...

Page 30: ...ktriker F re varje ingrepp m ste appa raten g ras sp nningsl s t ex genom att f rs kringarna los sas Anl ggningen g r inte varken i au tomatisk eller manuell drift N tsp nning saknas kontrollera s kri...

Page 31: ...e HighLogo 1 25 46 610 910 HighLogo 2 25 46 610 910 2 5 4 0 4 0 6 0 6 3 9 0 9 0 12 0 A 2 5 4 0 4 0 6 3 6 3 10 0 6 3 10 0 A vervakning vridf lt fasbortfall vid v nstervridf lt eller bortfall av en fas...

Page 32: ...32 HighLogo 1 00 E...

Page 33: ...30 32 an X3 P1 zu Br cken 9V Akku BT1 Hochwasser alarm I P1 HighLogo AUX 1 Motor schutz Pumpe 1 Getrennt GL AUS Potentialbehaftetes Alarmrelais Netzanschluss Pumpe 1 F1 6 3AT F2 2AT K4 L1 30 K1 BRX L...

Page 34: ...eichnete Verbindungen sind bauseits zu erstellen Der Luftschlauch f r die Niveauerfassung ist mit stetigem Gef lle zum Schacht zu verlegen 1 9V Akku BT1 Alarmrelais Sammelst r meldung Hochwasser alarm...

Page 35: ...35 HighLogo 1 LCXS...

Page 36: ...36...

Page 37: ...rstands Messung 0 5kOhm Reset Taster AUX 1 Motor schutz Pumpe 1 Motor schutz Pumpe 2 Getrennt GL AUS KT T GL SL HW I P2 50Hz Netz 1 N PE x 230V 1 5mm 1 K3 K2 Alarmrelais Sammelst r meldung max 5A 230V...

Page 38: ...38 HighLogo 2 00 2 910 1...

Page 39: ...39 HighLogo 2 00 2 910 2...

Page 40: ...40 HighLogo 2 LC 1...

Page 41: ...41 HighLogo 2 LC 2...

Page 42: ...42 HighLogo 2 LCXS 1...

Page 43: ...43 HighLogo 2 LCXS 2...

Page 44: ...er opz Q1 Opt main Switch Inter principal Fac Hoofdschakelaar Int principale F1 Safety barrier Barri re s curit Veiligheidsbarr Barr sicurezza SUOMI SVENSKA POLSKI Netz Verkkoliit nt N tanslutning Pod...

Page 45: ...eneral Manager R diger Rokohl Sales Manager 2011 65 EU RoHS 2014 30 EU EMC EN 55014 1 2006 A2 2011 EN 55014 2 1997 A2 2008 EN 61000 3 2 2014 EN 61000 3 3 2013 2014 35 EU LVD EN 60204 1 2006 AC 2010 EN...

Page 46: ...der eigen verantwoordelijkheid dat het product voldoet aan de gestelde richtlijnen PL Z pe n odpowiedzialno ci o wiadczamy e produkt odpowiada postanowieniom wymienionych dyrektyw RO Declar m pe propr...

Page 47: ...47...

Page 48: ...JUNG PUMPEN GmbH Industriestr 4 6 33803 Steinhagen Deutschland Tel 49 5204 170 Fax 49 5204 80368 eMail kd jung pumpen de...

Page 49: ...Stromkreis Die Barriere wird im Geh use der Pum pensteuerung untergebracht und verdrahtet Einsetzbar in die Pumpensteuerungen AD 23 910 X AD 25 910 XM AD 8 XME AD 12 XME BD 23 910 X BD 25 910 XM HIGHL...

Page 50: ...h her montieren WARTUNG Der Trockenlaufschutz ist eine wichtige Sicherheitseinrichtung f r den Explosionsschutz und muss mindestens 1x pro Jahr und in gewerblich genutzten Anlagen 2x pro Jahr auf korr...

Page 51: ...he following pump control units AD 23 610 X AD 25 610 XM AD 8 XME AD 12 XME BD 23 610 X BD 25 610 XM HIGHLOGO OLD 12 2017 AD 23 610 Ex 4 AD 25 ExM 3 AD 46 610 ExM 7 AD 8 ExME 3 AD 12 ExME 4 BD 23 610...

Page 52: ...p MAINTENANCE Dry running protection is an important safety device for explo sion protection and its good working order must be checked at least once a year and in commercially used systems twice a ye...

Page 53: ...intrinseca Essa viene installata nell alloggiamento del comando pompa e cablata Pu essere utilizzata per i seguenti comandi di pompe AD 23 610 X AD 25 610 XM AD 8 XME AD 12 XME BD 23 610 X BD 25 610 X...

Page 54: ...l inter ruttore a galleggiante pi alto MANUTENZIONE La protezione contro la marcia a secco un importante dispo sitivo di sicurezza per la protezione contro le esplosioni e il suo corretto funzionament...

Page 55: ...Sicherheitsbar riere von aktiven Teilen anderer Stromkreise muss mindes tens 50 mm Fadenma betragen ELEKTRISCHER ANSCHLUSS An die eigensicheren Klemmen d rfen Stromkreise der Zone 1 oder 2 angeschloss...

Page 56: ...ll monitored environment The distance between the intrinsically safe terminals of the safety barrier and the active parts of any other electrical cir cuits must be at least 50 mm string length ELECTRI...

Page 57: ...ti a sicurezza intrinseca della barriera di sicurezza dalle parti attive di altri circuiti deve essere di alme no 50 mm misura del filo COLLEGAMENTO ELETTRICO Ai morsetti a sicurezza intrinseca possib...

Page 58: ...4...

Page 59: ...5...

Page 60: ...6...

Page 61: ...7...

Page 62: ...8...

Page 63: ...9...

Page 64: ...zodpovednos vyhlasujeme e v robok sp a po iadavky uveden ch smern c SV Vi f rs krar att produkten p v rt ansvar r utf rd enligt g llande riktlinjer CE 121 17 1811 Steinhagen 15 11 2018 ______________...

Reviews: