Paragon Controls Inc,
Rev J 2/3/2021
Commonly Adjusted Variables
Object Description
Min
Max
Default
R/W
Address
Data
type
Data Value Descriptions
System 1 K-Factor
0.50
2.000
1
W
40013
4
*Note 1
System 2 K-Factor
0.50
2.000
1
W
40019
4
*Note 1
System 3 K-Factor
0.50
2.000
1
W
40025
4
*Note 1
SubSystem K-Factor
0.50
2.000
1
W
40031
4
*Note 1
System 1 Operating Range
0
*Note 2
*Note 2
W
40077
3
System 2 Operating Range
0
*Note 2
*Note 2
W
40085
3
System 3 Operating Range
0
*Note 2
*Note 2
W
40093
3
SubSystem Operating Range
0
*Note 2
*Note 2
W
40101
3
System 1 Number of Samples
1
99
30
W
40103
2
*Note 3
System 1 Sample Interval Time
1
10
1
W
40104
2
*Note 3
System 2 Number of Samples
1
99
30
W
40105
2
*Note 3
System 2 Sample Interval Time
1
10
1
W
40106
2
*Note 3
System 3 Number of Samples
1
99
30
W
40107
2
*Note 3
System 3 Sample Interval Time
1
10
1
W
40108
2
*Note 3
System 1 Low Alarm
0
999999
0
W
40125
3
System 1 High Alarm
0
999999
0
W
40127
3
System 1 Alarm Delay
0
999
0
W
40129
2
System 2 Low Alarm
0
999999
0
W
40132
3
System 2 High Alarm
0
999999
0
W
40134
3
System 2 Alarm Delay
0
999
0
W
40136
2
System 3 Low Alarm
0
999999
0
W
40139
3
System 3 High Alarm
0
999999
0
W
40141
3
System 3 Alarm Delay
0
999
0
W
40143
2
SubSystem Low Alarm
0
999999
0
W
40146
3
SubSystem High Alarm
0
999999
0
W
40148
3
SubSystem Alarm Delay
0
999
0
W
40150
2
System 1 Tagging
0
12
0
W
40197
6
*Note 4
System 2 Tagging
0
12
0
W
40203
6
*Note 4
System 3 Tagging
0
12
0
W
40209
6
*Note 4
SubSystem Tagging
0
12
0
W
40215
6
*Note 4
System 1 Temperature Source
1
3
1
W
40699
1 = Fixed, 2 = Variable, 3 = Network
System 2 Temperature Source
1
3
1
W
40700
1 = Fixed, 2 = Variable, 3 = Network
System 3 Temperature Source
1
3
2
W
40701
1 = Fixed, 2 = Variable, 3 = Network
System 1 Alarm Enable
0
1
0
W
40705
2
0 = Disabled, 1 = Enabled
System 2 Alarm Enable
0
1
0
W
40706
2
0 = Disabled, 1 = Enabled
System 3 Alarm Enable
0
1
0
W
40707
2
0 = Disabled, 1 = Enabled
SubSystem Alarm Enable
0
1
0
W
40708
2
0 = Disabled, 1 = Enabled
∆P1 Alarm Enable
0
2
0
W
40726
2
0 = Off, 1 = Low Trigger, 2 = Hi Trigger
∆P2 Alarm Enable
0
2
0
W
40727
2
0 = Off, 1 = Low Trigger, 2 = Hi Trigger
∆P3 Alarm Enable
0
2
0
W
40728
2
0 = Off, 1 = Low Trigger, 2 = Hi Trigger
∆P4 Alarm Enable
0
2
0
W
40729
2
0 = Off, 1 = Low Trigger, 2 = Hi Trigger
Note 1: K-Factor adjustment is done during system balancing to compensate for system effect in MTSE readings.
Note 2: System Operating Range and maximum Operating Range are dependent on numerous, application
specific parameters.
Note 3: Number of Samples and Sampling Interval Time effect response rate seen by sensor. Increasing interval
time will slow response and increasing number of samples will increase sample quantity for the rolling
average filter.
Note 4: String is 6 register width, 2 characters per register. 12 characters total + null terminator.
Example: System 1 Tagging = “AHU-1 SA ” would be 01 10 00 C4 00 06 0C 48 41 2D 55 20 31 41 53
20 20 20 20 46 EA