DRAFT
MTSE
IO&M Manual
33
Paragon Controls Inc,
Rev J 2/3/2021
MTSE Unit BACnet Protocol Implementation Conformance
Statement
Rev 2 1/05/2021
BACnet Standardized Device Profile (Annex L):
BACnet Application Specific Controller (B-ASC)
BACnet Interoperability Building Blocks Supported (Annex K):
DS-RP-B
DS-RPM-B
DS-WP-B
DS-WPM-B
DM-RD-B
DM-DDB-B
DM-DOB-B
DM-DCC-B
Segmentation Capability:
NONE
Standard Object Types Supported:
(See Table 1 for details)
Analog Input
Analog Output
Analog Value
Binary Input
Binary Output
Binary Value
Multistate Input
Multistate Value
CharacterString Value
Data Link Layer Options:
MS/TP master (Clause 9), baud rate(s): 9600, 19200, 38400, 76800
Device Address Binding:
NO
Networking Options:
NONE
Character Sets Supported:
ANSI 3.4
Supported Services:
ReadProperty
Execute
ReadPropertyMultiple
Execute
WriteProperty
Execute
WritePropertyMultiple
Execute
DeviceCommunicationControl
Execute
Who-Is
Initiate, Execute
I-Am
Initiate, Execute
Gateway:
This product does not support gateway functionality for any types of non-BACnet equipment/network(s).