DRAFT
MTSE
IO&M Manual
20
Paragon Controls Inc,
Rev J 2/3/2021
Min and Max Temperature
The minimum and maximum temperature range (scaling) will be entered in two respective boxes when
Variable is selected as the Temperature Source. This range will scale relative to the analog input with
minimum being 0V or 4mA and maximum being 5V, 10V, or 20mA, depending on the Analog Input
signal selected in Section 4.2.3.
Fixed Temperature Value
The fixed temperature can be entered or modified in this box when fixed is selected as the Temperature
Source.
The standard/default Fixed Value is 68˚F.
Temperature Units
The user can select between the temperature units of Fahrenheit or Celsius via toggle buttons.
Default
is Fahrenheit.
Altitude Selection
Allows user to select from two different atmospheric pressure standards, Altitude or Barometric. Actual
air density will be calculated accordingly dependent upon the selection. Toggling between the Altitude
Selection of Altitude and Barometric changes the user input field for the reference atmospheric pressure
between Elevation (left image) or Barometric (right image).
Default is altitude.
Elevation and Barometric Pressure
If the Altitude Selection is in Elevation, this box allows the user to enter a specific elevation in feet
above mean sea level for density corrections.
The standard/default value for elevation is 0 feet or sea
level.
If the Altitude Selection is in Barometric, this box allows the user to enter a specific barometric
pressure. The value entered will need to be converted to Inches of Mercury (in.Hg) for density
correction.
4.2.7. Alarm Options
High and Low alarms are available for each System in the MTSE to alert the user to a situation defined
on this menu page.