DRAFT
MTSE
IO&M Manual
35
Paragon Controls Inc,
Rev J 2/3/2021
Analog Value-
16
Controller 4 Output
No
No
• Description
• Eng Units
R/W
REAL
Min = 0
Max = 100
Binary Input-1
Digital Input 1
No
No
• Description
R
ENUMERATED
Binary Input-2
Digital Input 2
No
No
• Description
R
ENUMERATED
Binary Value-1
System 1 Alarm Enable
No
No
• Description
R/W
ENUMERATED
1: Off
2: On
Binary Value-2
System 2 Alarm Enable
No
No
• Description
R/W
ENUMERATED
1: Off
2: On
Binary Value-3
System 3 Alarm Enable
No
No
• Description
R/W
ENUMERATED
1: Off
2: On
Binary Value-4
Sub System Alarm Enable
No
No
• Description
R/W
ENUMERATED
1: Off
2: On
Binary Output-5
Digital Output 1
No
No
• Description
R/W
ENUMERATED
Binary Output-6
Digital Output 2
No
No
• Description
R/W
ENUMERATED
Multi State
Value-1
System 1 Engineering
Units
No
No
• Description
R/W
UNSIGNED
See
Table 2.
Note: Unit Selection Dependent on Multi State Value-9
Multi State
Value-2
System 2 Engineering
Units
No
No
• Description
R/W
UNSIGNED
See
Table 2.
Note: Unit Selection Dependent on Multi State Value-9
Multi State
Value-3
System 3 Engineering
Units
No
No
• Description
R/W
UNSIGNED
See
Table 2.
Note: Unit Selection Dependent on Multi State Value-9
Multi State
Value-4
Temperature Engineering
Units
No
No
• Description
R/W
UNSIGNED
1: F°
2: C°
Multi State
Value-5
System 1 Temperature
Source
No
No
• Description
R/W
UNSIGNED
1: Fixed
2: Analog
3: Network
Multi State
Value-6
System 2 Temperature
Source
No
No
• Description
R/W
UNSIGNED
1: Fixed
2: Analog
3: Network
Multi State
Value-7
System 3 Temperature
Source
No
No
• Description
R/W
UNSIGNED
1: Fixed
2: Analog
3: Network
Multi State
Value-8
Sub System Temperature
Source
No
No
• Description
R/W
UNSIGNED
1: Fixed
2: Analog
3: Network
Multi State
Value-9
Process Type 1
No
No
• Description
R/W
UNSIGNED
1: Standard Flow
2: Actual Flow
3: Standard Velocity
4: Actual Velocity
5: Pressure
Multi State
Value-10
Process Type 2
No
No
• Description
R/W
UNSIGNED
1: Standard Flow
2: Actual Flow
3: Standard Velocity
4: Actual Velocity
5: Pressure
Multi State
Value-11
Process Type 3
No
No
• Description
R/W
UNSIGNED
1: Standard Flow
2: Actual Flow
3: Standard Velocity
4: Actual Velocity
5: Pressure
Multi State
Input-1
System 1 Status
No
No
• Description
R
UNSIGNED
1 = Normal
2 = Low Alarm
3 = High Alarm
Multi State
Input-2
System 2 Status
No
No
• Description
R
UNSIGNED
1 = Normal
2 = Low Alarm
3 = High Alarm
Multi State
Input-3
System 3 Status
No
No
• Description
R
UNSIGNED
1 = Normal
2 = Low Alarm
3 = High Alarm