DRAFT
MTSE
IO&M Manual
14
Paragon Controls Inc,
Rev J 2/3/2021
SE
TUP
MENU
S
1. Operating Range
Enter Tagging Information for each system served
Toggle Select Area Type either Area or
Piezometer for each system
Enter Area or Piezometer Coefficient for each
system
Enter Operating Range for each system; Max
value that represents 100% of output
For Piezometer Coefficients that incorporate a
Standard Density term, toggle Std. Den. to Incld
2. K-Factor
Enter Balancer and MTSE flow measurements to
calculate a K-factor
Or enter K-factor directly
3. Analog I/O
Toggle select System Process Output 0-10V or 4-
20mA for each system
Toggle select System Temperature Input 0-5V, 0-
10V, or 4-20mA for each system
4. System Filters
Enter total Number of Samples for rolling average
calculation for each system
Enter Sampling Interval Time (time in seconds
between samples) for rolling average calculation
5. Network
Communications
Toggle select between BACnet MS/TP Master or
Modbus RTU Slave
Toggle select available Baud Rate
Enter the MAC Address or Modbus ID
Enter Instance Number (BACnet only)
6. Temperature and
Altitude
Toggle select where Temp Input will be obtained
between Fixed, Variable, or Network for each
system
If Fixed temp, enter Temp in last column. If
Variable, enter min and max Temp representing
min and max analog input for scaling
Toggle select between Altitude or Barometric
pressue for density correction
If Altitude selected, enter Elevation in feet; if
Barometric selected enter Pressure in in.Hg
Toggle select Termperaure Units between
degrees F or C
7. Alarms
Toggle Enable or Disable Alarms for each system
Enter Low and/or High Alarm value (in same
units) to be compared to a system's flow value
(0 is Off)
Enter Alarm Delay value; amount of time in
seconds before alarm is triggered
Enter Lockdown Percent (of Operating Range) for
each system; a zero value will be indicated when
below this percentage
Enter a Lockdown Delay value; amount of time in
seconds before a zero value is triggered
8. Units and Precision
Toggle select between Measurement Type: Std.
Flow, Act. Flow, Std. Velocity, Act. Velocity, or
Pressure for each system
Toggle select Units of measure corresponding to
the Measurement Type
Toggle select the Decimal Point location for
significant decimal figures for each system
9.
ΔP
Settings
(only if
ΔP is ordered
)
Enter
ΔP
Tagging information for each
ΔP
point
Toggle select Alarm trigger mode for each
ΔP
point
: Off, High Alarm, or Low Alarm
Enter Alarm Setpoint value (in same units)
Toggle select
ΔP Units of measurement