Baud Rate
The Baud Rate menu allows the user to set a BACnet network baud rate from 9.6K to 76.8Kbps or from
9.6K to 115.2Kbps for Modbus. The selected baud rate should match the network baud rate.
The
default is 38.4Kbps.
MAC Address
The MAC Address menu allows the user to set a device address when connecting to a BACnet network.
The MAC Code identifies each device on a branch of the network and can range from 2 to 127. The
MAC Code must be unique within a particular branch of a network however, MAC Codes can repeat if
on another branch of the network.
The default is 002.
Displayed only if BACnet is selected.
Instance Number
The Instance Number menu allows the user to set a unique device address when connecting to a BACnet
network. The Instance Number is a unique device ID that identifies the device on the entire network;
Instance Numbers cannot repeat within any part of a network and can range from a value of 1,002 to
4,194,302.
The default is 1002
.
Displayed only if BACnet is selected.
Modbus ID
The Modbus ID menu allows the user to enter the unique device address when connect to a Modbus
network. The range is from 001 to 254
. Default is 001. Displayed only if Modbus is selected.
4.2.6. Temperature Compensation & Altitude
This page is for configuring temperature and altitude values for density correction. The temperature and
altitude menu are shown below.
Temperature Source
The Temperature Source allows the user to select between three temperature input options (Fixed,
Variable, and Network) for the source of temperature for density correction calculations. If Fixed is
selected the temperature value entered in the Fixed box is used. If Variable is selected an external
analog temperature input signal from a temperature sensor is required (see Sections 4.2.3). If Network
is selected, the temperature input is obtained through network communications. The temperature value
is only displayed on the Normal Active Display if the Temperature Source is set to Variable or Network.
If Fixed is selected, temperature will not be displayed on the main screen.