DRAFT
MTSE
IO&M Manual
23
Paragon Controls Inc,
Rev J 2/3/2021
is selected. For example, if standard flow is selected, only standard flow units will be selectable for that
system. Changing the engineering units will not convert the values entered for Operating Range or
Alarms; new values will need to be entered in the correct units.
Default units is ACFM.
Standard Flow
Units
Actual Flow
Units
Standard Velocity
Units
Actual Velocity
Units
Pressure
Units
SCFM
ACFM
SFPM
AFPM
In. W.C.
SCFH
L/S
Sm/s
Am/s
Pa
SL/S
Am
3/
S
%
%
kPa
Sm
3
/S
Am
3/
M
mm W.C.
Sm
3
/M
Am
3/
HR
%
Sm
3
/HR
%
%
Decimal Points (Significant Figures)
Allows user to change number of digits shown to the right of the decimal point. When a new
engineering unit is selected, the Decimal Point will be automatically updated according to the table
below. The user can then toggle through moving the decimal point to the left with each press of the gray
box.
Significant Figures
Units
000000.
SCFM
SCFH
SL/s
Sm
3
/Hr
ACFM
AL/s Am
3
/hr All % Units
00000.0
Sm
3
/min
Am
3
/min SFPM AFPM.
Pa
0000.00
mm W.C.
000.000
Sm
3
/s
Am
3
/s
Sm/s
Am/s
Inch W.C
00.0000
kPa
4.2.9. ΔP Settings
ΔP Tagging
Selecting this box will provide a keypad popup to allow entry of unique ΔP tagging information. The
tagging information will be displayed on the Normal Active Display and any other place indicating ΔP
in the setup menus. Six characters can be entered as the ΔP tag.