communication values, and analog process output values for each system.
Default is 30 samples and a
sample interval time of 1 second.
Shown below is the System Filter Menus page.
For example, if the MTSE is measuring OA flow on a roof top unit and is experiencing large
fluctuations in readings caused by wind, slow the response time by increasing the number of samples
and increasing the interval time. Conversely, reduce the number of samples and/or interval time to make
the response time faster.
4.2.5. Network Communications
Modbus and BACnet communications are selectable in this menu page. Shown below is the Network
Communications page. The layout on the left is displayed if BACnet MS/TP is selected. The layout on
the right is displayed if Modbus is selected. See BACnet PIC statements and Modbus registers for
complete communication specifications in Attachment A and B, respectively.
Power must be cycled for network changes to take effect. Please turn off the MTSE at the power
switch (S1) for several seconds and then turn the unit back on after making changes to the below
network parameters.