Paragon Controls Inc,
Rev J 2/3/2021
High Flow Alarm
If any system alarm is enabled and the flow for that respective system exceeds the high flow alarm value
set in the setup menu Section 4.2.7 Alarms, then a High Flow Alarm will occur.
Low Flow Alarm
If any system alarm is enabled and the flow for that respective system falls below the low flow alarm
value set in the setup menu Section 4.2.7 Alarms, then a Low Flow Alarm will occur.