SC-HG1 Series FB Library Reference Manual for Mitsubishi MELSEC iQ-R series Sequencer
WUME-SCHG1IQRFB-1
47/184
Error code
■ List of error codes
Error code
(hexadecimal)
Description
Meaning
100
The Station No. (i_uStationNo) is
outside the valid range
For CC-Link master/local module
Set the Station No. (i_uStationNo) to a value from 1 to 64.
For CC-Link IE Field master/local module
Set the Station No. (i_uStationNo) to a value from 1 to 120.
101
The information derived from the input
Start I/O No.(i_uStartIONo) and the
Station No. (i_uStationNo) is not
SC-HG1-C or SC-HG1-CEF.
Check if the Start I/O No.(i_uStartIONo) and the Station
No. (i_uStationNo) settings correctly indicate the target
communication unit.
104
Set to a controller where Set Controller
(i_uSetController) is set to 0 or does not
exist
Make the value of Set Controller (i_uSetController) greater
than 0.
Check if the setting is not applied to a controller beyond the
maximum number of connected units. Also, check if the
15th bit of Set Controller (i_uSetController) is not ON.
106
Teaching Steps (i_uTeachStep) is outside
the valid range
Set Teaching Steps (i_uTeachStep) to a value not greater
than 2.
107
"1-point teaching" is selected and Shift
Amount (i_udShiftAmount) is outside
the valid range.
Selecting "1-point teaching " requires you to set Shift
Amount (i_udShiftAmount) to a value within the valid
range.
108
Input Signal (i_bInputSignal) is ON and
Execution Command (i_bEN) is ON
Turn OFF Input Signal (i_bInputSignal) and then turn ON
Execution Command (i_bEN)