SC-HG1 Series FB Library Reference Manual for Mitsubishi MELSEC iQ-R series Sequencer
WUME-SCHG1IQRFB-1
57/184
Error code
(hexadecimal)
Description
Meaning
200
Remote READY flag OFF
Check whether or not an error has occurred in the
communication unit.
Check if the Start I/O No.(i_uStartIONo) and the Station
No. (i_uStationNo) settings correctly indicate the target
communication unit.
201
Execution Command (i_bEN) turned OFF
before normal or error completion
Check that Normal Completion (o_bOK) or Error
Completion (o_bErr) has turned ON and then turn OFF
Execution Command (i_bEN). This error code is output
also when Execution Command (i_bEN) is intentionally
turned OFF before completion.
202
Execution Command (i_bEN) was turned
from ON to OFF and then turned from
OFF to ON while Execution Status
(o_bENO) was ON
Check that Execution Status (o_bENO) turned OFF and
then turn ON Execution Command (i_bEN).
FFFF
Module error occurrence
Check the Module Error Code (o_ud16ModuleErrId).
For information on module error codes, see "Appendix
2.4 Module error code (o_u16ModuleErrId) list".