SC-HG1 Series FB Library Reference Manual for Mitsubishi MELSEC iQ-R series Sequencer
WUME-SCHG1IQRFB-1
141/184
(2) Setting module parameters (when using the CC-Link master/local module)
Next, configure the module parameters.
Configure "CC-Link configuration" and "link refresh settings" under "basic settings".
Navigation window → Parameter → Module information → (Start XY): RJ61BT11 → Module parameter
Figure 1.5.3-5: Module parameters (basic settings)
Under "CC-Link configuration", set the communication unit to be connected.
You can also drag a "
General Remote Device Station " from the module list at the right and down it onto the configuration
below.
At this time, you can restrict the setting items by using CSP+ of SC-HG1-C.
Ensure that the red-framed information you configure or check here is the same as configured on the communication unit.
The mode settings for SC-HG1-C are restricted depending on the operation mode you configure. Refer to the following
table to configure the settings.
CC-Link mode2 and CC-Link mode3 uses the extended cyclic function and therefore the mode setting does not work in
"Ver.1 mode".
CC-Link mode1
CC-Link mode2
CC-Link mode3
Ver.1 mode
○
×
×
Ver.2 mode
○
○
○
Configure the values for setup items for each operation mode as instructed in the table below.
CC-Link mode1
CC-Link mode2
CC-Link mode3
Version
Ver.1
Ver.2
Ver.2
Number of occupied stations 4-station occupied 2-station occupied 4-station occupied
Extended cyclic settings
-
Eightfold setting
Fourfold setting