SC-HG1 Series FB Library Reference Manual for Mitsubishi MELSEC iQ-R series Sequencer
WUME-SCHG1IQRFB-1
90/184
Error code
■ List of error codes
Error code
(hexadecimal)
Description
Meaning
100
The Station No. (i_uStationNo) is
outside the valid range
For CC-Link master/local module
Set the Station No. (i_uStationNo) to a value from 1 to 64.
For CC-Link IE Field master/local module
Set the Station No. (i_uStationNo) to a value from 1 to 120.
101
The information derived from the input
Start I/O No.(i_uStartIONo) and the
Station No. (i_uStationNo) is not
SC-HG1-C or SC-HG1-CEF.
Check if the Start I/O No.(i_uStartIONo) and the Station
No. (i_uStationNo) settings correctly indicate the target
communication unit.
104
Set to a controller where Set Controller
(i_uSetController) is set to 0 or does not
exist
Make the value of Set Controller (i_uSetController) greater
than 0.
Check if the setting is not applied to a controller beyond
the maximum number of connected units. Also, check if the
15th bit of Set Controller (i_uSetController) is not ON.
10F
The Low Threshold (i_dLowThreshold)
value is higher than the High Threshold
(i_dHighThreshold) value.
Correct the settings so that the Low Threshold
(i_dLowThreshold) value is lower than the High Threshold
(i_dHighThreshold) value.
110
Low Threshold (i_dLowThreshold) is
outside the valid range
Specify a value within the valid range.
111
High Threshold (i_dHighThreshold) is
outside the valid range
Specify a value within the valid range.
112
Hysterisis Value (i_udHysteresis) is
outside the valid range
Specify a value within the valid range.
113
Hysterisis Value (i_udHysteresis) is
larger than the difference between Low
Threshold (i_dLowThreshold) and High
Threshold (i_dHighThreshold)
Make Hysterisis Value (i_udHysteresis) smaller than the
difference between Low Threshold (i_dLowThreshold) and
High Threshold (i_dHighThreshold)