
FP3 MEWNET - TR
Chapter7 - 2. Page.97
93
LED status
Steps to take
x
When communication is not possible with any slave station
<Master station COM.: OFF, Slave stations 1 and 2 POWER: OFF,
COM: OFF, Other LEDs: normal status>
Slave station 1
Slave station 2
POWER
COM.
ALARM
POWER
COM.
ALARM
No power supply
No power supply or
Incorrect terminal station
Master station
RUN
PROG.
TEST
BREAK
ERROR
BATT.
ALARM
COM.
ALARM
<FP3/FP10S
CPU>
<FP3
transmitter
master unit>
S
Check that power is
properly supplied to
the slave stations.
S
Set the terminal
station correctly.
<Master station COM.: OFF, Slave stations 1 and 2 COM.: ON,
Other LEDs: normal status>
POWER
COM.
ALARM
Slave station 1
Slave station 2
POWER
COM.
ALARM
Disconnection
Master station
RUN
PROG.
TEST
BREAK
ERROR
BATT.
ALARM
COM.
ALARM
<FP3/FP10S
CPU>
<FP3
transmitter
master unit>
S
Check the wiring
between master and
slave station.
x
When the remote I/O control function cannot be used
<Master station COM.: ON, Slave stations 1 and 2 COM.: ON,
Other LEDs: normal status>
POWER
COM.
ALARM
Slave station 1
Slave station 2
POWER
COM.
ALARM
Master station
RUN
PROG.
TEST
BREAK
ERROR
BATT.
ALARM
COM.
ALARM
<FP3/FP10S
CPU>
<FP3
transmitter
master unit>
S
Set operation mode
selector No. 1 on the
FP3 transmitter master
unit to the OFF
position.
7 -2. Remote I/O Control When an Error Occurs
Summary of Contents for FP10S
Page 32: ...26 ...
Page 54: ...48 ...
Page 76: ...70 ...
Page 116: ...110 ...
Page 151: ......
Page 152: ...ACG M0076 1 ...