FP3 MEWNET - TR
Chapter6 - 2. Page.84
80
6-2. FP-M/FP1 Master Station and
FP3/FP10S Master Station
1. FP-M and FP3/FP10S
By connecting the FP-M transmitter master board and FP3 transmitter master unit, I/O data can be exchanged between
the two master stations. The I/O points allocated to master stations A and B correspond one to one. When an output is
generated from one master station, the corresponding input point of the other master station turns ON.
1) Wiring and setting method
J
FP - M and FP3/FP10S
FP3 transmitter master unit
setting at 32 inputs: X0 to X1F,
32 outputs: Y20 to Y3F
FP - M transmitter master board
setting at 32 inputs: X110 to X12F,
32 outputs: Y110 to Y12F
ON
OFF
ON
OFF
X0
Y40
Master
station B
Y40 of master B
turns ON
FP3/FP10S CPU
Operation mode
selector
OFF
ON
1
2
3
4
5
6
7
8
ON
X2
Y110
Y110: ON
→
X0: ON
1
2
3
4
5
6
7
8
ON
↓
Operation mode selector
OFF
ON
FP - M
control
board
Master
station A
When X2 of master A
turns ON
Transmission cable
(Twisted pair cable
or 2 - conductor cable)
OFF OFF OFF
x
Connect the RS485 interfaces of the FP-M transmitter master board and FP3 transmitter master unit with a
transmission cable.
x
Set the operation mode selectors of each master station as shown below.
<Master A>
<Master B>
FP-M Selector No. 1: OFF, No. 3: ON
FP3/FP10S Selector No. 1: ON
Notes:
x
Either master station can be set as master B. However, be sure to pair up two stations as master A and
master B.
x
When the I/O link function is used, do not connect a slave station.
x
It is recommended that the FP - M transmitter master board and FP3 transmitter master unit have the same
number of I/O points. To set the number of I/O points, use the operation mode selectors, and follow the same
procedure as for the I/O allocation for remote I/O slave stations.
x
For the I/O point setting of operation mode selector of the FP3 transmitter master unit, see page 50, “4 - 1.
Operation Mode Setting.”
x
For the setting of operation mode selector of the FP - M transmitter master board, see the “FP - M/FP1
MEWNET - TR Technical Manual.”