FP3 MEWNET - TR
Chapter8 - 1. Page.116
112
8-1. Specifications
1. General
Item
Description
Ambient temperature
0
°
C to + 55
°
C (32
°
F to 131
°
F)
Ambient humidity
30 % to 85 % RH (non - condensing)
Storage temperature
- 20
°
C to + 70
°
C ( - 4
°
F to 158
°
F)
Storage humidity
30 % to 85 % RH (non - condensing)
Vibration resistance
10 Hz to 55 Hz, 1 cycle/min: double amplitude of 0.75 mm (0.030 in.),
10 min on 3 axes
Shock resistance
98 m/s
2
(10 G) or more, 4 times on 3 axes
Noise immunity
1,000 Vp - p with pulse width, 50 ns and 1
P
s
(based on in - house measurements)
Operating environment
Must be free from corrosive gases and excessive dust.
2. FP3 MEWNET-TR System
Item
Description
Communication method
Two - lines, half - duplex
Synchronization method
Asynchronous system
Communication path
2 - conductor cable or twisted pair cable
Transmission distance
Max. 700 m (2,296.59 ft.) with twisted pair cable
Max. 400 m (1,312.34 ft.) with 2 - conductor cable
See page 45 for about the transmission cable.
Communication speed
0.5 Mbps
Input/output response
time
I/O response time is determined by the number of slave stations (FP I/O
transmitter units and expansion FP I/O terminal units).
See page 128, “8 - 5. Transfer Time,” for details about the I/O response time.
Controllable I/O points
Max. 128 inputs and 128 outputs/FP3 transmitter master unit
Max. 2,048 inputs and 2,048 outputs (sixteen FP3 transmitter master units)/
FP3 CPU
Max. 3,072 inputs and 3,072 outputs (twenty - four FP3 transmitter master units)/
FP10S CPU
Interface
RS485
Communication error
checking method
Self - diagnosis data checking method
3. Performance
1) FP3 transmitter master unit
Item
Description
Controllable I/O points
*
The controllable I/O points are selected by the operation mode selector
(selector numbers 5, 6, 7, and 8).
Input:
Select from 0, 32, 64 or 128 points.
Output: Select from 0, 32, 64 or 128 points.
I/O occupation points
The total number of input and output points that are set
Current consumption
*
130 mA or less
Connection method
Terminal block (M3.5 screw)
Weight
Approx. 240 g/8.466 oz.
* The total number of controllable I/O points should not be set higher than the number of I/O points of the FP3/FP10S CPU.
The total current consumption of the units used should not exceed the rated output current of their power supply unit.
See page 8 for about the limitations on unit installation.
8 -1. Specifications
Summary of Contents for FP10S
Page 32: ...26 ...
Page 54: ...48 ...
Page 76: ...70 ...
Page 116: ...110 ...
Page 151: ......
Page 152: ...ACG M0076 1 ...