FP3 MEWNET - TR
Chapter1 - 4. Page.13
9
2. Slave Stations
x
The slave stations that can be used for remote I/O control are as follows:
Type
Part number
FP I/O transmitter unit
4 - input
AFP87525
8 - input
AFP87521
16 - input
AFP87522
4 - output
AFP87527
8 - output
AFP87523
16 - output
AFP87524
J
Combinations of units set for the slave station (factory setting)
The FP3/FP10S MEWNET -TR can be connected with more than one FP I/O transmitter unit within the range of control
I/O point numbers set by the operation mode selector of the master station (FP3 transmitter master unit).
However, the maximum number of slave stations is 16 units for input and 16 units for output.
< Example of combination >
When setting the control I/O point numbers to 128 for input and 128 for output using the operation mode selector.
x
System configuration with only the 16 -point type
FP I/O transmitter units
- 16 -input type
×
8 units (128 inputs)
- 16 -output type
×
8 units (128 outputs)
x
System configuration with only the 8 -point type
FP I/O transmitter units
- 8 -input type
×
16 units (128 inputs)
- 8 -output type
×
16 units (128 outputs)
x
When the system is configured with only 4 -point units, the maximum of 16 input units and 16 output units can be used
even if the setting is made for 128 input points and 128 output points. Therefore, only 64 points can be used for each,
as shown below.
- 4 -input
×
16 units (64 inputs)
- 4 -output
×
16 units (64 outputs)
J
Expansion on the slave station side
x
The following units can be added to the slave station.
Type
Part number
Expansion FP I/O terminal unit
8 - input
AFP87425
p
16 - input
AFP87426
8 - output
AFP87427
16 - output
AFP87428
The slave station can be connected with one expansion FP I/O terminal unit to increase the number of I/O points.
Note:
x
The 4 - point type slave station (FP I/O transmitter unit) cannot be connected with the expansion FP I/O
terminal unit.
<Example>
Total I/O points : 24 inputs
FP I/O
transmitter unit
Expansion
FP I/O
terminal unit
8 - input type
16 - input type
Total I/O points : 16 points (8 inputs / 8 outputs)
FP I/O
transmitter unit
Expansion
FP I/O
terminal unit
8 - output type
8 - input type
x
See page 46, “5. Slave Station Expansion” for details about the expansion of slave stations.
1 -4. Combinations