FP3 MEWNET - TR
Chapter2 - 2. Page.18
14
J
Operation monitor LEDs
LED
Description
COM.
Flashing:
ON:
Flashing slowly:
OFF:
Normal communication status (flashes in approx. 0.2 s intervals)
Waiting for communication
A communication error occurred at the slave station.The normal slave station
continues I/O control operation when operation mode selector No.2 is set to
the ON position. (flashes in approx. 1 s intervals)
A communication error with a slave station
ALARM
Flashing:
ON:
OFF:
Station number setting error or operation mode selector Nos. 5 to 8 are all
set to the OFF position
Error on FP3 transmitter master unit
Normal
J
Operation mode selector settings
Selector
Function
Description
Selector position
Selector
number
Function
Description
1
2
3
4
5
6
7
8
1
System
configuration
l
ti
Remote I/O control disabled,
master B of I/O link
ON
g
selection
Remote I/O control enabled,
master A of I/O link
OFF
2
Output operation
condition during a
i
ti
Hold (continues I/O control
operation)
ON
g
communication error Output OFF
OFF
3 and 4
Not used
-
-
5 and 6
Input point
l
ti
f l
0 point
OFF OFF
p
p
selection of slave
station
32 points
ON
OFF
station
64 points
OFF
ON
128 points
ON
ON
7 and 8
Output point
l
ti
f l
0 point
OFF OFF
p
p
selection of slave
station
32 points
ON
OFF
station
64 points
OFF
ON
128 points
ON
ON
Notes:
x
The operation mode selectors are all set to the OFF position when shipped.
x
The operation mode selector’s right side is “OFF (
)” and the left side is “ON (
).”
x
Be sure the power is OFF when changing the selector position.
2 -2. Master Station
OFF
ON
1
2
3
4
5
6
7
8