2) FP I/O transmitter unit
Operation mode selector
OFF
ON
1
2
3
4
Selector
Function
Description
Selector position
Selector
number
Function
Description
1
2
3
4
1
Communication
d
l
ti
(1:1)
×
n communication
ON
mode selection
1:1 communication
OFF
2
System configuration
selection
This unit is regarded as a slave
station.
ON
This unit is not regarded as a slave
station.
OFF
3
Output operation
condition during
Hold (continues I/O communication)
ON
condition during
a communication error
Output OFF
OFF
4
Terminal station setting
Terminal station
ON
Not a terminal station
OFF
Notes:
x
The operation mode selectors are all set to the OFF position when shipped.
x
The operation mode selector’s upper state is “ON (
)” and the lower state is “OFF (
).”
x
Be sure the power is OFF when changing the switch position.
2. Station Number Selector
x
The I/O numbers to be allocated to each slave station are determined by the slave station number setting.
Since each I/O number is assigned to a single slave station number, set each slave station with the slave station number
that corresponds to the I/O numbers you wish to allocate.
x
To set a slave station number, turn the station number selector of the FP I/O transmitter unit using a slotted screwdriver.
Example: Setting station number 2
Set “2”.
Station
number
selector
Slotted
screwdriver
8 -3. Settings