FP3 MEWNET - TR
Chapter1 - 2. Page.8
4
J
Total transmission distance of up to 700 m
When the network is connected with twisted pair cable, the maximum transmission distance is 700 m (2,296.59 ft).
When a 2 -conductor cable is used, the maximum transmission distance is 400 m (1,312.34 ft).
Example : FP3/FP10S MEWNET -TR system
Master
station
Slave
station
FP I/O transmitter units
FP I/O transmitter units
Total transmission distance :
Max. 700 m/2,296.59 ft. with twisted pair cable
Max. 400 m/1,312.34 ft. with 2 - conductor cable
Total transmission distance :
Max. 700 m/2,296.59 ft. with twisted pair cable
Max. 400 m/1,312.34 ft. with 2 - conductor cable
FP3 transmitter master units
FP3/FP10S CPU
J
Selection of the slave station with the most suitable number of I/O points to match the application
The FP I/O transmitter unit is available with 4, 8 and 16 I/O points for use as a slave station to allow the most suitable
system configuration. The 8 -point and 16 -point FP I/O transmitter units can be combined with the expansion FP I/O
terminal unit to establish a system with different numbers of input and output points.
Type
Description
Part number
FP I/O
transmitter
4 - input
Rated power supply voltage: 24 V DC
So ce i p t
AFP87525
transmitter
unit
8 - input
Source input
AFP87521
unit
16 - input
AFP87522
4 - output
Rated power supply voltage: 24 V DC
T a sisto NPN ope collecto o tp t
AFP87527
8 - output
Transistor NPN open collector output
Max. load current: 0.5 A/point, 1 A/common
AFP87523
16 - output
Max. load current: 0.5 A/point, 1 A/common
AFP87524
Expansion FP
I/O terminal
8 - input
Rated power supply voltage: 24 V DC
So ce i p t
AFP87425
I/O terminal
unit
16 - input
Source input
AFP87426
unit
8 - output
Rated power supply voltage: 24 V DC
Transistor NPN open collector output
AFP87427
16 - output
Transistor NPN open collector output
Max. load current: 0.5 A/point, 1 A/common
AFP87428
Note:
x
The FP I/O transmitter units (4 - input and 4 - output type) cannot be combined with expansion FP I/O terminal
units.
1 -2. Features
Summary of Contents for FP10S
Page 32: ...26 ...
Page 54: ...48 ...
Page 76: ...70 ...
Page 116: ...110 ...
Page 151: ......