FP3 MEWNET - TR
Chapter7 - 1. Page.94
90
7-1. Checking the CPU When an Error
Occurs
x
If a communication error or an error in the FP3 transmitter master unit occurs, check the LED status for the FP3 transmitter
master unit and the FP I/O transmitter unit.
See pages 91 to 98 and 103 to 107 for details about the operation monitor LED status when an error occurs.
x
When a communication error occurs, the CPU of the FP3/FP10S detects the error using a self-diagnostic function.
J
Checking method
1) The operation monitor LEDs of the CPU show the following LED status.
RUN
PROG.
TEST
BREAK
ERROR
BATT.
ALARM
RUN LED:
ON
ERROR LED: ON
Other LEDs: OFF
2) With the FP3 CPU, special internal relay R9002 turns ON.
3) Self-diagnostic error code “E40” can be read by the NPST-GR software and FP programmer II.
Error code “E40” is stored in special data register DT9000 for the FP3, and in special data register DT90000 for
the FP10S.
See the “FP3/FP10S HARDWARE Technical Manual” for details about the special data registers and self-diagnostic
error codes.
4) The slot No. of the FP3 transmitter master unit that is generating an error can be checked with special data registers
DT9002 and DT9003.
Example:
x
When an error is generated in the FP3 transmitter master unit mounted in slot No. 3 of the master backplane.
Special data registers: DT9003, DT9002
·
·
15
12
0 0 0 0
·
·
11
8
0 0 0 0
·
·
7
4
0 0 0 0
·
·
3
0
0 0 0 0
Bit position
DT9003
·
·
15
12
·
·
11
8
·
·
7
4
·
·
3
0
Slot number
·
·
15
12
0 0 0 0
·
·
11
8
0 0 0 0
·
·
7
4
0 0 0 0
·
·
3
0
1 0 0 0
Bit position
DT9002
·
·
15
12
·
·
11
8
·
·
7
4
·
·
3
0
Slot number
7 -1. Checking the CPU When an Error Occurs
Summary of Contents for FP10S
Page 32: ...26 ...
Page 54: ...48 ...
Page 76: ...70 ...
Page 116: ...110 ...
Page 151: ......
Page 152: ...ACG M0076 1 ...