FP3 MEWNET - TR
Chapter3 - 1. Page.32
28
3-1. Installation
1. Master Station
1) Limitations on location
x
The FP3 transmitter master unit can be installed in any slot of the master backplane or expansion backplane.
Example:
Available
installing location
FP3 transmitter master unit
FP3/FP10S CPU
Power supply unit
Master backplane
2) Limitations on unit installation
x
A CPU can be installed with more than one FP3 transmitter master unit.
However, the following limitations must be observed.
- The total current consumption of the units used must not exceed the rated output current of their power supply unit.
The current consumption of the FP3 transmitter master unit is 150 mA.
- The total number of I/O points used by the FP3 transmitter master units must not exceed the number of I/O points
of the CPU that is used.
x
See the “FP3/FP10S HARDWARE Technical Manual” for details about limitations on current consumption and I/O
points.
Combination example:
x
When using an FP3 CPU to control an FP3 transmitter master unit for which 128 input points and 128 output points
are selected, the following unit combinations are possible.
- Number of FP3 transmitter master units: 16
- Controllable I/O points
Input:
2,048 points
Output: 2,048 points
- Current consumption
Basic system on master backplane (8 slots):
1,680 mA
Expansion system on expansion backplane (8 slots): 1,300 mA
3 -1. Installation