FP3 MEWNET - TR
Chapter7 - 2. Page.101
97
LED status
Steps to take
x
Communications error
When operation mode selector No. 2 of the FP3 transmitter master unit is OFF
(when the setting is made to terminate the remote I/O control of all slave stations in
the event of a communications error)
<Master station ERROR: ON, COM.: Flashing slowly,
Slave station 1 POWER: OFF, COM.: OFF, Slave station 2 COM.: OFF,
Other LEDs: normal status>
POWER
COM.
ALARM
Slave station 1
Slave station 2
POWER
COM.
ALARM
No power supply
Master station
RUN
PROG.
TEST
BREAK
ERROR
BATT.
ALARM
COM.
ALARM
<FP3/FP10S
CPU>
<FP3
transmitter
master unit>
S
Check that power is
properly supplied to
slave station 1.
<Master station ERROR: ON, COM.: Flashing slowly,
Slave stations 1 and 2 COM.: OFF, Other LEDs: normal status>
POWER
COM.
ALARM
Slave station 1
Slave station 2
POWER
COM.
ALARM
Disconnection
Master station
RUN
PROG.
TEST
BREAK
ERROR
BATT.
ALARM
COM.
ALARM
<FP3/FP10S
CPU>
<FP3
transmitter
master unit>
S
Check the wiring.
<Master station ERROR: ON, COM.: Flashing slowly,
Slave station 1 COM.: OFF, Slave station 2 COM.: OFF, ALARM: ON,
Other LEDs: normal status>
POWER
COM.
ALARM
Slave station 1
Slave station 2
POWER
COM.
ALARM
Communications
error
Master station
RUN
PROG.
TEST
BREAK
ERROR
BATT.
ALARM
COM.
ALARM
<FP3/FP10S
CPU>
<FP3
transmitter
master unit>
S
Communications error
on slave station 2.
See page 101.
7 -2. Remote I/O Control When an Error Occurs