FP3 MEWNET - TR
Chapter6 - 2. Page.86
82
2. FP1 and FP3/FP10S
By connecting the FP1 transmitter master unit and FP3 transmitter master unit, I/O data can be exchanged between the
two master stations. The I/O points allocated to master stations A and B correspond one to one. When an output is
generated from one master station, the corresponding input point of the other master station turns ON.
1) Wiring and setting method
J
FP1 and FP3/FP10S
Master
station A
FP1 control unit
X2
Y70
Y70: ON
→
X0: ON
Operation mode selector
1 2 3 4 5 6
OFF
ON
ON
OFF
Transmission cable
(Twisted pair cable or
2 - conductor cable)
When X2 of master A
turns ON
ON
OFF
ON
OFF
X0
Y4F
Master
station B
Y4F of master B
turns ON
FP3 transmitter master unit
(setting at 32 inputs/32 outputs)
FP3/FP10S CPU
Operation mode
selector
OFF
ON
1
2
3
4
5
6
7
8
ON
FP1 transmitter master unit
(setting at 32 inputs/32 outputs)
OFF OFF
x
Connect the RS485 interfaces of the FP1 transmitter master unit and FP3 transmitter master unit with a transmission
cable.
x
Set the operation mode selectors of each master station as shown below.
<Master A>
<Master B>
FP1 Selector No. 1: OFF, No. 3: ON
FP3/FP10S Selector No. 1: ON
Notes:
x
Either master station can be set as master B. However, be sure to pair up two stations as master A and
master B.
x
When the I/O link function is used, do not connect a slave station.
x
It is recommended that master A and master B have the same number of I/O points. To set I/O points, use
the operation mode selectors, and follow the same procedure as for the I/O allocation for remote I/O slave
stations.
x
For the setting of the operation mode selector of the FP3 transmitter master unit, see page 50, “4 - 1.
Operation Mode Setting.”
x
For the setting of the operation mode selector of the FP1 transmitter master unit, see the “FP - M/FP1
MEWNET - TR Technical Manual.”