Operation Manual
FT128 Rev 2.4
79
Downloading in progress….
▓ ▓ ▓ “progress bar”
When the download is completed and the control unit restarts, a fault message will be
shown in the display:
Download completed successfully
Control unit will now restart
FAULT: Restart code 25
DD-MM-YYYY
HH:MM
Code 25 indicates a normal restart after the SSD download.
Acknowledge the restart fault. If the download was unsuccessful, another fault will be
generated:
FAULT: Site specific data (SSD)
Date:-DD-MM Time: HH:MM
This text message means that the SSD has not been downloaded successfully i.e. a new
download must be performed.
18.2.2
User Definable Text Messages Download
Each alarm point, zone and zone line input should have a unique user definable alarm text
programmed via
EBLWin
. When a fire alarm is activated e.g. an addressable alarm point,
the presentation number (Zone – Address) will be shown on the first row in the FT128
display and in all the external display units 1728 and 1736 with its alarm text.
All alarm texts, up to 40 alphanumeric characters each, are created and downloaded via
EBLWin
(SSD Download). See Technical / Programming manual, chapter "Alarm texts".
A fault message for an alarm point, zone, zone line input will also show the text message
(software ≥ V2.0.0).
18.3
Download Software (System Firmware)
Note: When existing system requires software upgrade, first, logon to the Control Unit
using a compatible EBLWin (or Win128) software version with the existing firmware
version in FT128 then conduct SSD backup to save the existing Site Specific Data file.
This must be performed prior to any software download.
The latest software version of EBL128 system software
is factory downloaded before
delivery. Due to continual development and improvement, different S/W versions may be
found.
FT128 can be upgraded with a new S/W version, downloaded on site via EBLWin as well
as remote display units 1728 and 1736. The valid (current) S/W version of the main board
4556 is shown in menu H4/U7 or via EBLWin (Control unit pop-up menu; Software
version…).
•
If the FDCIE time differs more than 60 minutes to the time shown in the PC, a
dialog box will display when logon is performed. Via this dialog box, the PC time
can be used to update the FDCIE time.
•
A user that is defined to have access to Web-server (not the FDCIE) can have a
password containing between 6 and 10 characters (not only digits).
Before commencing a firmware download, ensure you have a copy of the current SSD and
be save in the latest EBLWin software version.
55
The software (firmware) is the system software and always uses “EBL” abbreviation.
Summary of Contents for Firetracker FT128
Page 1: ...Operation Manual FT128 Rev 2 4 For Software V2 4 x FT128 FDCIE MA350 April 2018 ...
Page 2: ...2 This page has deliberately been left blank ...
Page 33: ...Operation Manual FT128 Rev 2 4 33 Figure 25 Field Module Enclosure BAFMES ...
Page 144: ...Operation Manual FT128 Rev 2 4 144 Figure 26 FT128 General Arrangement for 19 Rack System ...
Page 145: ...Operation Manual FT128 Rev 2 4 145 Figure 27 FT128 Standard Block Wiring Diagram ...
Page 146: ...Operation Manual FT128 Rev 2 4 146 Figure 28 NZFT128 Block Wiring Diagram for NZ ...