Operation Manual
FT128 Rev 2.4
57
Programmable outputs for quiet alarm is required e.g. 3361 outputs controlling fan
operation i.e. any output with a control expression containing the trigger conditions "Quiet
Alarm Zone" or "Quiet Alarm Zone Address".
Quiet Alarms are automatically reset, non-brigade call alarm and do not activate any
common alarm output.
14.9
Acknowledged and Isolated Alarm (for only NZ)
Note: Acknowledged or Isolated alarm is a fire alarm function used only in New Zealand
convention.
14.9.1
Acknowledged Alarm
A fire alarm presented in the LCD can be acknowledged by pressing the yellow button
“Fault acknowledge” (P6).
Acknowledged alarms are indicated in the fire alarm list on the LCD by “ACK” in front of
the alarm. This indication is the only difference between a fire alarm and acknowledged
alarm.
Acknowledged alarms "ACK" have to be reset same as normal fire alarms "ALM".
14.9.2
Isolated Alarm (for only NZ)
A normal fire alarm “ALM” or an acknowledged alarm “ACK” presented on the LCD can be
isolated as follow:
When the “New Zealand FB Silence Switch” (outside switch) is restored i.e. from the
activated to non-activated position, any fire alarm and acknowledged alarm will be isolated
(disabled).
Isolated alarms are indicated in the fire alarm list on the LCD by “ISO” in front of the alarm.
Isolated alarms do not activate any control outputs, output for routing equipment (Fire
Brigade TX), FT128 buzzer and the LEDs “Fire” in the FDCIE.
Isolated alarm “ISO” have to be reset same as normal fire alarms "ALM".
Isolated alarms have to be re-enabled via menu H2/B5-B6 before they can activate a new
fire alarm.
Summary of Contents for Firetracker FT128
Page 1: ...Operation Manual FT128 Rev 2 4 For Software V2 4 x FT128 FDCIE MA350 April 2018 ...
Page 2: ...2 This page has deliberately been left blank ...
Page 33: ...Operation Manual FT128 Rev 2 4 33 Figure 25 Field Module Enclosure BAFMES ...
Page 144: ...Operation Manual FT128 Rev 2 4 144 Figure 26 FT128 General Arrangement for 19 Rack System ...
Page 145: ...Operation Manual FT128 Rev 2 4 145 Figure 27 FT128 Standard Block Wiring Diagram ...
Page 146: ...Operation Manual FT128 Rev 2 4 146 Figure 28 NZFT128 Block Wiring Diagram for NZ ...