Operation Manual
FT128 Rev 2.4
113
24.4
Display Current Consumption in Unit (H5/A4)
Power Supply (Control Unit)
Voltage - xx.xx V:
The 24V measured by the CPU on the main board. Corresponds to the
output voltage at the power supply outputs on connector J1.
Earth voltage - xx.xx V
: Measured from 0V (connector J1:14) to earth.
Current from power supply: xxx mA:
The total current consumption (including the
charging current at 24V) for the control unit when it is connected to the mains (230 V AC),
i.e. this function is not working by battery backup.
BATTERY
Voltage: xx.xx V:
The battery voltage at connector J2:4-5
.
Charging current: x mA:
The battery charging current for the control unit (FDCIE).
Resistance in battery circuit: xxxxx mΩ:
During the battery resistance check the voltage
is measured with
and without a resistor. A resistance > 500 mΩ will result in a "Low battery
capacity" fault. Checked every 4th hour.
Charging:
The battery charging current.
Low capacity voltage difference:
During the battery capacity check the voltage is
measured with and without a resistor. A difference between these two voltages > 2100 mV
will result in a "Low battery capacity" fault. This is checked every 4th hour.
Action
Text in display
Comments
"Access"
Log on to FT128 as shown in
page 35.
Scroll to menu H5.
Service
ACCEPT? H5
"A"
Calibration of supervised outputs
ACCEPT? A1
Scroll to menu A4
Display current consumption in unit
ACCEPT? A4
"A"
Current consumption unit: XXXX mA
Charging: XXXX mA
Press "
" for the second
information window.
“
”
Low capacity
Press "
" for the first
information window.
"Return"
Display current consumption in unit
ACCEPT? A4
Scroll or press "Return" to
H5.
"Return"
Service
ACCEPT? H5
Scroll or press "Return".
Notes: Each window is updated continuously.
67
This window will not be visible until 4 hours after the CIE. is powered and the batteries have to be connected.
Summary of Contents for Firetracker FT128
Page 1: ...Operation Manual FT128 Rev 2 4 For Software V2 4 x FT128 FDCIE MA350 April 2018 ...
Page 2: ...2 This page has deliberately been left blank ...
Page 33: ...Operation Manual FT128 Rev 2 4 33 Figure 25 Field Module Enclosure BAFMES ...
Page 144: ...Operation Manual FT128 Rev 2 4 144 Figure 26 FT128 General Arrangement for 19 Rack System ...
Page 145: ...Operation Manual FT128 Rev 2 4 145 Figure 27 FT128 Standard Block Wiring Diagram ...
Page 146: ...Operation Manual FT128 Rev 2 4 146 Figure 28 NZFT128 Block Wiring Diagram for NZ ...