Operation Manual
FT128 Rev 2.4
121
26 Perform ZONE TEST (Test Mode) (H7)
Normally, zones are tested during the monthly test via menu H1, see page 85. Via this
menu (H7) it is possible to perform the zone test.
Up to 99 zones can be in set in test mode.
In test mode, only the alarm points are tested, i.e. no outputs (no sounders) will be
activated during the test. (Alarm devices can be tested via menu H8/S6 and any output
via menu H8/S9 or via EBLWin when you are logged on).
If a real fire alarm is activated by an alarm point not in test mode, the normal fire alarm
functions will be activated, i.e. fire alarm presentation, outputs (OWS or sounders)
activated, routing equipment (Fire Brigade TX) activated, etc.
There will be an automatic termination of the test mode one hour after the latest tested
alarm point / zone.
Note: If the door in FT128 is left open, the output(s) for external strobe or alarm bell
might be disabled (if set in EBLWin).
Action
Text in display
Comments
"Access"
Log on to FT128 as shown in
page 35.
Scroll to menu H7.
Perform ZONE TEST
ACCEPT? H7
"A"
Set zone in test mode
ACCEPT? D1
D1
= Sub menu to set a
zone in test mode.
"A"
Set zone: 00 in test mode
Start test: ACCEPT
Write the zone number and
press "A".
e.g. "01"
"A"
Zone 01 in test mode
LED "Test mode" (L9) will
light up.
"A"
Set zone: 00 in test mode
Start test: ACCEPT
If more zones to be set in
test mode, do as above, else
press "Return".
“Return”
Set zone in test mode
ACCEPT? D1
The zone(s) will stay in test mode until the test mode is terminated
. The test mode will also be automatically
terminated 60 minutes after the last testing in the zone.
Perform the test as quickly as possible, since the output(s) for routing equipment (Fire Brigade TX) are disabled
(also the parts of the zones in test mode, not visible for the test personnel, are disabled).
In order to shorten the testing time, any time delay for the detectors / zones in test mode will be "disabled", i.e. fire
alarm will be detected faster than normal.
In the tested alarm point, the LED will light up and the alarm point will be automatically reset after about ten
seconds. The alarm will also momentarily be shown in the FT128 display.
A sensor in test mode will not be able to activate fault.
Set zone in test mode
ACCEPT? D1
To terminate the test mode,
the menu D1 has to be open.
Press "
" or "2" to open
menu D2.
"
"
or
Set zone in test mode
ACCEPT? D2
Press "↑" to end the test
mode.
Summary of Contents for Firetracker FT128
Page 1: ...Operation Manual FT128 Rev 2 4 For Software V2 4 x FT128 FDCIE MA350 April 2018 ...
Page 2: ...2 This page has deliberately been left blank ...
Page 33: ...Operation Manual FT128 Rev 2 4 33 Figure 25 Field Module Enclosure BAFMES ...
Page 144: ...Operation Manual FT128 Rev 2 4 144 Figure 26 FT128 General Arrangement for 19 Rack System ...
Page 145: ...Operation Manual FT128 Rev 2 4 145 Figure 27 FT128 Standard Block Wiring Diagram ...
Page 146: ...Operation Manual FT128 Rev 2 4 146 Figure 28 NZFT128 Block Wiring Diagram for NZ ...