Operation Manual
FT128 Rev 2.4
68
FT128 cannot communicate with the unit.
Check the cable, all connections,
etc. Is correct / complete SSD downloaded (via EBLWin).
Check the address
and the S/W mode in the unit (or edit the SSD).
FAULT: No reply, expansion board x
Valid for the 8-Zone Expansion Board 4580, 8 relays exp. board 4581 and the I/O
exp. board 4583 mounted in FT128. Also valid for the I/O Matrix board 4582
connected on the COM loop, i.e. mounted outside the FDCIE
FT128 cannot communicate with the board. Check / edit the address. Check the
cables / connections.
FAULT: Output Sx
This is valid for the FT128 supervised voltage outputs S0 and S1.
If the output is programmed for sounders or OWS (type Alarm devices), it is also
indicated by LED "
Fault / Disablements
Alarm devices" (L13) blinking.
If the output is programmed for a Fire Brigade TX (type Routing equipment), it is
also indicated by LED "
Fault / Disablements
Fire Brigade TX" (L15) blinking.
•
Calibration not performed via menu H5/A1.
•
Short / open circuit on the connected cable / equipment.
•
Blown fuse "F8" (S0) or "F6" (S1) on the main board 4556.
•
Connected equipment might be "missing".
•
End-of-line resistor(s) missing or not correct (1-5 resistors 33K)
NOTE: The calibrated value has to be in the range 4K7 – 50K
FAULT: Output x expansion board x
A fault on supervised output x on the expansion board (4583) with address x.
If the output is programmed for sounders (type Alarm devices), it is also indicated
by LED "
Fault / Disablements
Alarm devices" (L13) blinking.
If the output is programmed for Fire Brigade TX (type Routing equipment), it is
also indicated by LED "
Fault / Disablements
Fire Brigade TX" (L15) blinking.
•
Calibration not performed via menu H5/A1.
•
Short / open circuit on the connected cable / equipment.
•
Blown fuse "F1" (Output 0) or "F2" (Output 1) on the 4583 board.
•
Connected equipment might be missing.
•
End-of-line resistor(s) missing or not correct value (1-5 x 33K).
Note: The calibrated value has to be in the range 4K7-50K.
FAULT: Output x, techn addr xxx
Valid for outputs of COM loop output unit 3364.
If the output is programmed for sounders or OWS (type Alarm devices), it is also
indicated by LED "
Fault / Disablements
Alarm devices" (L13) blinking.
If the output is programmed for Fire Brigade TX (type Routing equipment), it is
also indicated by LED "
Fault / Disablements
Fire Brigade TX" (L15) blinking.
•
Calibration not performed via menu H5/A1.
•
Short / open circuit break on the connected cable / equipment.
•
Connected equipment might be missing.
•
End-of-line capacitor(s) or resistor(s) missing or not correct value,
1-5
capacitors (470 nF). (Valid for 3364 only)
Note: The calibrated value has to be in the range 470nF – 5 x 470nF (2350nF).
Summary of Contents for Firetracker FT128
Page 1: ...Operation Manual FT128 Rev 2 4 For Software V2 4 x FT128 FDCIE MA350 April 2018 ...
Page 2: ...2 This page has deliberately been left blank ...
Page 33: ...Operation Manual FT128 Rev 2 4 33 Figure 25 Field Module Enclosure BAFMES ...
Page 144: ...Operation Manual FT128 Rev 2 4 144 Figure 26 FT128 General Arrangement for 19 Rack System ...
Page 145: ...Operation Manual FT128 Rev 2 4 145 Figure 27 FT128 Standard Block Wiring Diagram ...
Page 146: ...Operation Manual FT128 Rev 2 4 146 Figure 28 NZFT128 Block Wiring Diagram for NZ ...