New check loop function
The control unit will find all units that are connected on the selected COM loop.
The search is always performed in the A-direction and stops at the first fault found.
A fault; a break (cut-off) or short circuit on the loop, will be shown graphically.
Repair the fault and press start to resume. Units containing isolators are numbered
(sequence number). These units will always come in the correct order. Units
without short circuit isolators are visualized in their correct segment. Segments are
divided by units containing short circuit isolator. Segments are indicated by red or
blue colour. For more details, refer to FT128 Technical / Programming manual.
•
Loop Units serial numbers
During check loop or auto-addressing the loop unit’s serial number is read and
displayed in EBLWin as well as saved in SSD. The loop units currently supporting
this function are 4400I, 4418, 4433*, 4439*, 4461, 4462, 4479, 4480*, 4481*,
4482* and 4487* (* feature will be introduced in production during 2018). All future
units will also support the function.
•
Local Alarm Acknowledgement
Up to 5 alarm points can be defined per Addressable local alarm acknowledge unit
4445. In the new version an alarm point can be either a zone/address or a whole
zone containing several smoke detectors. Also, the wireless smoke detector 4611
and the multi detectors 4400 in advanced mode and 4400I can be used for alarm
acknowledgement.
•
Version control for SSD download
When the Download SSD window is opened in EBLWin, the EBLWin checks that
the SSD file originates from the SSD in the control units and opens a dialog if
otherwise (to prevent from unintentionally download an older version of the SSD).
•
Improved disablement of smoke detection in 4400/4400I
The smoke detection of a multi detector 4400 or 4400I can now be disabled by the
menu system (H2/B1).
When the smoke detection of a multi detector 4400 or 4400I is disabled it’s
indicated as a disablement.
•
New output type: 'Alarm device for evacuation'
The new output type 'Alarm devices for evacuation' works the same as the current
type 'Alarm devices' except that the outputs are not affected by the push button
'Silence alarm devices'. This is a violation of AS4428.3.
•
Interlocking
The interlocking function is changed so that an output belonging to an interlocking
combination can be of any type.
•
Enhanced service signal
A service signal will be given when a 4400I detector is to be changed because of
long time use. The time limits vary with country regulations.
•
Service mode
When the system is in some kind of 'Service mode', the spanner symbol used for
indicating 'Service signal' will flash. The system is in 'Service mode' when at least
one of the following is valid:
o
A COM loop is disconnected
o
A COM loop is in service mode
o
When Check loop, Auto address loop etc. is in progress
o
SSD download is in progress
The timeout for automatic reset of a COM-loop in service mode has been changed
from 15 min to one hour.
Summary of Contents for Firetracker FT128
Page 1: ...Operation Manual FT128 Rev 2 4 For Software V2 4 x FT128 FDCIE MA350 April 2018 ...
Page 2: ...2 This page has deliberately been left blank ...
Page 33: ...Operation Manual FT128 Rev 2 4 33 Figure 25 Field Module Enclosure BAFMES ...
Page 144: ...Operation Manual FT128 Rev 2 4 144 Figure 26 FT128 General Arrangement for 19 Rack System ...
Page 145: ...Operation Manual FT128 Rev 2 4 145 Figure 27 FT128 Standard Block Wiring Diagram ...
Page 146: ...Operation Manual FT128 Rev 2 4 146 Figure 28 NZFT128 Block Wiring Diagram for NZ ...