Operation Manual
FT128 Rev 2.4
67
Fault is activated 1-300 minutes after:
•
Loss of mains, i.e. no 230 V
AC
•
Blown mains fuse
•
Blown fuse "F1" on the main board 4556
FAULT: Mains, external power supply
This is valid for external power supply equipment, which has a fault output
connected to a programmable input in FT128 system.
The fault is activated 1-300 minutes after the input is activated.
•
Loss of mains, i.e. no 230 V AC to the ext. power supply equipment.
•
Blown mains fuse.
•
Check the programmable input connections.
FAULT: Mains, techn address xxx
3366 / 3364
This is valid for the external power supply unit 3366 and the addressable 2 voltage
outputs unit 3364, connected on the COM loop. The fault is activated 1-300
minutes after:
•
Loss of mains, i.e. no 230 V
AC
to the 3366 unit.
•
Blown mains fuse.
•
Fuse F1 blown on the 3366 unit's charger board.
•
3364 unit:
o
(/Mains OK) not connected to the 3366 unit (J7:4) or 0 V.
o
"no mains signal" from the 3366 unit.
The time delay of this fault activation is programmable via EBLWin. Default value
is 30 minutes.
FAULT: No reply zz-aa
Press
to
see the technical address.
FAULT: No reply techn. address xxx
zz-aa
= Zone address,
xxx
= COM loop address
The unit the unit cannot be found by the control unit.
•
Check the unit's COM loop address (with programming tool 3314/4414).
•
Check the downloaded site specific data (SSD).
•
The unit might be faulty.
•
Detector might be removed (un-plugged) from its base.
•
Double break or short-circuit on the COM loop.
(Note: There will also be a fault message "FAULT: Cut-off loop…." or "FAULT:
Short-circuit loop….".).
FAULT: No reply AAU x
FAULT: No reply EPU x
Alert Annunciation Unit 1736
External Presentation Unit 1728
FT128 cannot communicate with the unit.
Check the cable, all connections,
51
The time is programmable in EBLWin. Default value depending on convention.
Summary of Contents for Firetracker FT128
Page 1: ...Operation Manual FT128 Rev 2 4 For Software V2 4 x FT128 FDCIE MA350 April 2018 ...
Page 2: ...2 This page has deliberately been left blank ...
Page 33: ...Operation Manual FT128 Rev 2 4 33 Figure 25 Field Module Enclosure BAFMES ...
Page 144: ...Operation Manual FT128 Rev 2 4 144 Figure 26 FT128 General Arrangement for 19 Rack System ...
Page 145: ...Operation Manual FT128 Rev 2 4 145 Figure 27 FT128 Standard Block Wiring Diagram ...
Page 146: ...Operation Manual FT128 Rev 2 4 146 Figure 28 NZFT128 Block Wiring Diagram for NZ ...