Operation Manual
FT128 Rev 2.4
59
shown (e.g. a fault message), for priority order see section 3.4.2.2 Information Priority
Order page 19.
All outputs (for fire alarm) are reset, i.e. de-activated.
15.2.3
Single Reset with Automatic Disablement
Similar to "Single reset" but includes the encapsulation function.
Normally when an alarm point or zone having activated fire alarm is reset whilst still is in
alarm status, it will activate a new fire alarm within 20 seconds.
When "Single with automatic disablement" reset is performed, an alarm point or zone, still
in alarm status, will not only be reset but also disabled, i.e. it will not activate a new fire
alarm within 20 seconds. It has to be re-enabled via menu H2/B6 (see page 93) before it
can activate a new fire alarm. (This function, set via EBLWin, is a violation to AS7240-2
standard).
LED "Disablements" (L8) is indicating one or more disablements in the system.
When "All" or "Single" reset is used, "automatic disablement" (encapsulation function) can
be used by pressing "Reset" (P4) and approx. 0.1 sec. later also press "Alarms queued"
(P1) and hold them pressed for > 0.5 sec. The alarm point or the whole zone (conventional)
currently shown in the display will be reset and disabled.
15.3
Test Mode Alarm Reset
Test mode alarm is automatically reset after approx. 10 seconds.
15.4
Acknowledged and Isolated Alarm (for only NZ) Reset
Acknowledged alarms "ACK" or isolated alarm “ISO” have to be reset same as normal fire
alarms "ALM".
15.5
Heavy Smoke / Heat Alarm Reset
If a heavy smoke / heat alarm has been activated, it will be reset at the same time as the
corresponding fire alarm is reset. Also, the output(s) will be reset, i.e. de-activated.
15.6
Alert Annunciation Alarm Reset
Regarding the function, see chapter "Alert Annunciation Alarm (AA Alarm) page 54 and
FT128 Technical / Programming manual, chapter "Alert Annunciation".
Reset of the AA alarm can be performed via push button "Reset" on an AA unit 1736 or in
FT128. AA alarms will be reset all at a time.
Note: Reset via an AA unit (1736) is only possible during the investigation time and only
if the alarm is an AA alarm (not normal fire alarms). If more than one AA alarm is
activated, they will be reset all at the same time.
15.7
Co-Incidence Alarm Reset
Co-incidence alarm is automatically resets 5 minutes after the alarm point / zone is no
longer in alarm status or by the Reset button (P4).
15.8
Delayed Alarm
The Delayed alarm will be automatically reset if the alarm point during the delay time
countdown is no longer in alarm state or when a normal fire alarm is activated (i.e. when
the delay time has run out).
Summary of Contents for Firetracker FT128
Page 1: ...Operation Manual FT128 Rev 2 4 For Software V2 4 x FT128 FDCIE MA350 April 2018 ...
Page 2: ...2 This page has deliberately been left blank ...
Page 33: ...Operation Manual FT128 Rev 2 4 33 Figure 25 Field Module Enclosure BAFMES ...
Page 144: ...Operation Manual FT128 Rev 2 4 144 Figure 26 FT128 General Arrangement for 19 Rack System ...
Page 145: ...Operation Manual FT128 Rev 2 4 145 Figure 27 FT128 Standard Block Wiring Diagram ...
Page 146: ...Operation Manual FT128 Rev 2 4 146 Figure 28 NZFT128 Block Wiring Diagram for NZ ...