Operation Manual
FT128 Rev 2.4
93
21.6
Re-Enable Zone / Address (H2/B6)
Disabled alarm points (zone – address) are listed in menu H4/U1.
Re-enabling via this menu has higher priority than automatic re-enabling.
A zone will be presented as ZZ - 00 (ZZ=01-99).
Alarm points within a Zone disabled via the "New Zealand FB Silence Alarms Bulgin key"
(outside switch), have to be re-enabled via menu B5 or B6 before they can activate a new
alarm.
When all alarm points have been re-enabled, the LED "Disablements" (L8) will be
extinguished, if there are no other disablements.
If there is nothing to re-enable,
--- List is empty ---
will be shown.
Action
Text in display
Comments
"Access"
Log on to FT128 as
shown in page 35.
Scroll to menu H2:
Disable or re-enable
ACCEPT? H2
"A"
Disable zone
ACCEPT? B1
Scroll to menu B6.
Re-enable zone-address
ACCEPT? B6
"A"
Re-enable zone: 01 Address: 01
ACCEPT? L
L
=A list in which you
can scroll.
Press "A" to accept.
You will stay in this list
until all zone-addresses
are re-enabled or press
"Return" to menu B6.
"A" (to re-enable)
or
"Return"
Re-enable zone-address
ACCEPT? B6
If more re-enabling shall
be done, continue like
above. If not, scroll or
press "Return" to menu
H2.
"Return"
Disable or re-enable
ACCEPT? H2
Scroll or press "Return".
Summary of Contents for Firetracker FT128
Page 1: ...Operation Manual FT128 Rev 2 4 For Software V2 4 x FT128 FDCIE MA350 April 2018 ...
Page 2: ...2 This page has deliberately been left blank ...
Page 33: ...Operation Manual FT128 Rev 2 4 33 Figure 25 Field Module Enclosure BAFMES ...
Page 144: ...Operation Manual FT128 Rev 2 4 144 Figure 26 FT128 General Arrangement for 19 Rack System ...
Page 145: ...Operation Manual FT128 Rev 2 4 145 Figure 27 FT128 Standard Block Wiring Diagram ...
Page 146: ...Operation Manual FT128 Rev 2 4 146 Figure 28 NZFT128 Block Wiring Diagram for NZ ...