Operation Manual
FT128 Rev 2.4
9
Conventional detector
A detector with only two statuses, i.e. normal or fire alarm. The
detector has a "closing contact" and a series alarm resistor
(560 Ohm). Normally plugged in a conventional detector base
CDB (see below), which is connected to a conventional zone
line input. Some types are water proof types and cannot be
plugged in the standard base, it is connected directly to a zone
line. An end-of-line device has to be connected in the last unit
on the conventional zone line.
Conventional Detector Base (CDB)
A conventional detector is plugged in a CDB, connected to a
conventional zone line input.
Addressable
A unit with a built-in address device. Each unit is individually
identified, handled and indicated in the FDCIE. (The unit can
be an I/O unit with a zone line input, to which one or more
conventional "alarm points" can be connected.)
Conventional zone line input
Input intended for one or more conventional alarm points. End-
of-line device in the last alarm point on the zone must be fitted.
Output unit
Addressable unit with programmable control outputs.
Connected to the COM loop (see below).
Output / Control output
Defined or programmable function. Relay output or voltage
output (supervised or non-supervised), in the FDCIE or an
output unit connected to the COM loop.
Short circuit isolator (ISO)
Addressable unit for automatic disconnection of a COM loop
segment (see below) in case of short circuit on the loop. As per
AS1670.1, one isolator is required every 40 alarm points on the
COM loop or every zone.
Remote Display Unit (RDU)
Addressable unit (RS485 line) for fire alarm presentation
(including user definable alarm text), alert annunciation, etc.
Two types are normally used: External presentation unit 1728
(EPU) and alert annunciation unit 1736 (AAU).
Note:
An optional RS485 communication module (chip) must
be fitted in order to interface up to 8 display units (1728 /
1736), end of line resistor must be set via a jumper link on the
last unit. For more information, refer to the technical manual of
1728 and 1736
COM loop
Loop = twisted pair cable, to which all the addressable units
can be connected. Starts in the FDCIE and returns back to the
FDCIE.
Control Unit / C.U. / FDCIE
Control Unit = Fire Detection Control and Indicating Equipment
(FDCIE) = Unit to which the alarm points are connected (via
e.g. a COM loop). Indicates on the front fire alarm, fault
conditions, etc.
Fire Brigade Panel (FBP)
The fire brigade panel is an integral part of FT128 intended for
fire alarm, fault and disablement presentation, etc. The FBP
compromises the top part of the front display. Intended for fire
alarm presentation and for the fire brigade personnel.
Control panel (CP)
A part of the FT128 front display, intended for the building
occupier / officer, service personnel, etc., to "communicate"
with the Control Unit. It comprises the bottom part of the front
display.
Nuisance alarms
False or unwanted alarms
LED
LED (Light Emitting Diode) = Yellow, green or red optical
indicator ("lamp").
External Indicator / RIL
A unit with a red LED connected to a base (ASB / CDB) or a
detector with an output for a remote indicator RIL.
Lit when the built-in LED in the detector / base is lit.
Display / LCD
LCD (Liquid Crystal Display) = Display (in the FDCIE or Display
unit) for presentation of fire alarms, fault messages, etc.
Normally alphanumeric characters and backlight.
Door open (Door / Key switch)
In FT128 there is a door switch, which is activated when the
FDCIE door is open. Door open feature can be used to disable
Summary of Contents for Firetracker FT128
Page 1: ...Operation Manual FT128 Rev 2 4 For Software V2 4 x FT128 FDCIE MA350 April 2018 ...
Page 2: ...2 This page has deliberately been left blank ...
Page 33: ...Operation Manual FT128 Rev 2 4 33 Figure 25 Field Module Enclosure BAFMES ...
Page 144: ...Operation Manual FT128 Rev 2 4 144 Figure 26 FT128 General Arrangement for 19 Rack System ...
Page 145: ...Operation Manual FT128 Rev 2 4 145 Figure 27 FT128 Standard Block Wiring Diagram ...
Page 146: ...Operation Manual FT128 Rev 2 4 146 Figure 28 NZFT128 Block Wiring Diagram for NZ ...