ELC500 Control unit
110
■
Setup for Fixed-time demand (Moving average power method)
Item
Description
(a)
Name
Set name for demand control pattern
<Set range> 32-letter or less
(b)
Trigger
Set trigger from the registered trigger.
It works alarm function at this trigger, it works alarm function.
(c)
Period
Set demand period.
<Initial>30 min
<Set range>15 / 30 / 60
(d)
Alarm mask time
Set alarm mask time.
<Initial> 0 min
<Set range> 0 to 10
(e)
Use the data of the previous
period for demand
estimation.
Select use the function, it calculates estimated demand
using the incline of power in the previous period, or not.
<Initial> without check = not available
(f)
Control demand value
Set control demand value
<Initial> 0 kW
<Set range> 0 to 999999999999999
(g)
Limit control demand value
Set limit control demand value
<Initial>0 kW
<Set range> 0 to 999999999999999 kW
(h)
Target demand value
Set target demand value
<Initial>0 kW
<Set range>0
~
999999999999999 kW
(i)
Switch moving average time Select use the function, that it switches period 1st half and
2nd half for calculate demand value increasing rate to
estimate dimmed, or not
<Initial> Yes