ELC500 Control unit
61
[8] Through connection
Set to use the function to pass MEWTOCOL communication command from LAN port to serial port.
Item
Description
(a)
Use through function
Select use the function or not.
<Initial> without check = not available
(b)
Communication method
Set communication method.
<Initial> TCP/IP
<Set range> TCP/IP / UDP/IP
(c)
Port No. (Local station)
Set port number of LAN port to use for output a command to
serial port.
<Initial> Through connection(COM0): 60017
Through connection(COM1): 60018
Through connection(COM2): 60019
<Set range> 1 to 65535
(d)
Disconnect time with no
Communication *1
Set disconnect time during the communication.
Disconnection time exceeds the set time, it will disconnect
automatically.
<Initial> 60 sec
<Set range> 1 to 3600
*1 Only when ‘TCP/IP’ is selected for communication method.
Point
When ‘Use through function’ of Through connection (COM0) is available, a command to
LAN port is passed to COM0.
Note
- Through function supports only MEWTOCOL communication.
- When the station number is EE, it doesn’t through. It responses as ELC500.
(a)
(b)
(c)
(d)