ELC500 Control unit
25
■
Exclusive tool for rod terminal
Manufacture
Model No.
Phoenix Contact Co.
CRIMPFOX6(1212034)
■
Recommended cable for RS-232C transmission line
Type: Multi-conductor cable with shield
Conductor
Insulator
Size
Resistance (at 20
℃
)
Material
Thickness
0.3 mm
2
(AWG22) or more
Max.58.8
Ω
/km
chloroethylene
Max. 0.3 mm
Cable diameter
Applicable cable
Section
Approx. 6.6 mm
Onamba
ONB-D6x0.3mm
2
■
Recommended cable for RS-422 transmission line
Cable
Conductor
Insulator
Cable
diameter
Applicable cable
Size
Resistance
(at 20
℃
)
Material
Thickness
Twisted-
pair
with
shield
1.25 mm
2
(AWG16)
or more
Max.16.8
Ω
/km
Polyethylene
Max.
0.5 mm
Approx.
8.5 mm
HITACHI
KPEV-S
1.25 mm
2
×
1P
Belden Inc. 9860
0.5 mm
2
(AWG20)
or more
Max.33.4
Ω
/km
Polyethylene
Max.
0.5 mm
Approx.
7.8 mm
HITACHI
KPEV-S
0.5 mm
2
×
1P
Belden Inc. 9207
VCTF
0.75 mm
2
(AWG18)
or more
Max.25.1
Ω
/km
PVC
Max.
0.6 mm
Approx.
6.6 mm
VCTF
0.75 mm
2
×
2C
(JIS)
Cable
Section
Twisted-pair
with shield
VCTF
Note
- Use shielded type twist cables.
- Use only one type of the transmission cable. Do not mix the different type of cable.
- Use twist pair cables under a bad noise environment.
- Be sure to connect with daisy chain the RS-485 transmission line between each unit.
Do not use a splitter.
Conductor Insulator
Jacket
Shield
Jacket
Conductor Insulator
Shield
Conductor
Insulator
Jacket